8.3.2 Outdoor unit and indoor units' P Q E communication
Communication wiring design and installation should adhere to the following requirements:
2
0.75mm
three-core shielded cable should be used for communication wiring. Using other types of cable can lead to
interference and malfunction.
Do not bind the communication line, refrigerant piping and power cable together.
 When the power cable and communication line are laid in parallel, the distance between the two lines must be 5cm or
more to prevent signal source interference.
 The P Q E communication wires should be connected one unit after another in a daisy chain from the outdoor unit to
the final indoor unit as shown in Figure 3-8.5. At the final indoor unit, a 120Ω resistor should be connected between
the P and Q terminals. After the final indoor unit, the communication wiring should NOT be continued back to the
outdoor unit – that is, do not attempt to form a closed loop.
 The P and Q communication wires should NOT be connecting to E.
 The shielding nets of the communication wires should be connected together and grounded. Grounding can be
achieved by connecting to the metal casing adjacent to the P Q E terminals of the outdoor unit electrical control box.
 All IDUs in a system must be powered through a uniform power supply so that they can be powered on or off at the
same time.
 The communication wiring (P, Q, E) must through the magnetic ring from the main board to the IDUs.
 Applicable standards: EN 55014-1 and EN 55014-2. The communication line must be shielded wire.
Figure 3-8.5: P Q E communication wiring configuration – IDUs uniform power supplied
RS-485(P Q E) communication
L1+La+Ln≤1200m,Communication wiring 3*0.75mm
ODU
P Q
E
L1
Main control board
Q
E
P
Shield layer must
be grounded
Connect to the ODU PQE
2
N L
Circuit breaker
Distribution box
1# IDU
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
· · ·
P Q
E
L
L
L
L
N
N
N
La
(n-1)# IDU
...
P Q E
V8 Mini R410A VRF 50Hz
Communication wire
Power wire
Distribution box
n# IDU
P Q E
Ln
Resister
L
L
L
L
93