G. Vent Diagrams
1. Top Vent - Horizontal Termination
One Elbow
Note: Use SLP Series
components only.
Fire Risk.
• When using SLP-HRC-SS and SLP-HRC-ZC-SS
termination caps on top vented fi replaces, a two
foot minimum vertical vent section is required
before installing fi rst elbow.
Figure 4.7
16
WARNING**
Note: There MUST be a 25% reduction
in total H when using fl ex vent except
when using the simple up and out
installation (see Figure 4.6).
Heatilator • MDV3732 Installation Manual • 2386-980 Rev. D • 11/16
V
Minimum**
1
1 ft.**
305 mm
1-1/2 ft.** 457 mm
2-1/2 ft.
762 mm
3-1/2 ft.
1.1 m
4-1/2 ft.
1.4 m
H
MAX. =15 ft. (4.6 m)
1
V
+ H
MAX. = 40 ft. (12.2 m)
1
1
** See Warning.
H
1
H
Maximum
1
1 ft.**
305 mm
2 ft.
610 mm
4 ft.
1.2 m
6 ft.
1.8 m
15 ft.
4.6 m
V
1