Hisense AS-07HR4SYDTG Service Manual page 18

Table of Contents

Advertisement

5
.
CONTROL
MODE
5
.
CONTROL
MODE
4.2.1 This mode could be selected by the remote control
4.2.2 The 4-way reversing valve will be stopped under this mode.
4.2.3 During this mode, the temperature setting, air volume and air flow
direction could be adjusted.
During the appliance run in normal condition, the room's temperature
can be adjusted by 1℃ up and down base on the setting temperature, the
compressor operation diagram is shown as following.
When the temperature dropped, the compressor will be power on.
4.2.4 Overcooling protection control
When the indoor coil pipe temperature is lower than 3℃ and higher than
-7℃ during Cooling or Dry operation
high and outdoor fan turn off. After the temperature recovers to 7℃, the air
conditioner turn to run in normal condition. When the indoor coil pipe
temperature falls below –7℃ during COOLING or DRY operation for 3
minutes, the compressor and outdoor fan motor turn OFF. When the indoor
pipe temperature recovers to 5℃ and the compressor has been stopped for
3 minutes, the compressor and outdoor fan motor will be turned ON.
4.2.5 Indoor fan operation
(1) When room temperature is higher than 35℃, the compressor is
stopped for 1 min then turn on, (when the compressor ceased for 3 min
protection, the indoor fan should be turn on immediately)
(2)When the indoor fan keep in running condition, this operation state
could be controlled by the remote control with High, Median, Low and
Automatic setting.
(3)When the appliance is set Automatic condition in the Cool mode for
the first time, the fan speed will run at Low setting. After that, temperature
and fan speed is shown as following.
Compressor power ON
The setting temp. minus 1℃
Compressor power OFF
Compressor power ON
The setting temp. plus 1℃
Compressor power OFF
for 3 min, indoor fan speed turns to