11. Installation
Outdoor Units
Choosing the installation location
• Do not place the outdoor unit on its side or upside down. Failing to do so may cause the compressor
lubrication oil to run into the cooling circuit and lead to serious damage to the unit.
• Install the unit in a well-ventilated location away from strong winds.
• Install the unit in a location that would not obstruct any passageways or thoroughfares.
• Install the unit in a location that would not inconvenience or disturb your neighbors, as they could be
affected by the noise or the airflow coming from the unit.
• Install the unit in a location where the pipes and the cables can be easily connected to the indoor unit.
• Install the unit on a flat, stable surface that can withstand the weight of the unit. Otherwise, the unit can
generate noise and vibration during operation.
• Install the unit so that the air flow has adequate clearance, as noted in the manual.
CAUTION
• This device must be installed according to all national, state, and local codes and requirements.
• If your outdoor unit exceeds a net weight of 132.2 lb(60 kg), do not install it on a suspended wall, but
stand it on a floor.
• The reliability of our product cannot be guaranteed under conditions of -13 ℉ (-25 ℃) or less.
• When installing the outdoor unit in coastal applications, make sure that it is not directly exposed to sea
breeze. If you cannot find an adequate place free from direct sea breeze, construct a protection wall or a
protective fence.
− Install the outdoor unit in a place (such as near buildings etc.) where it can be screened from sea
breeze. Failure to do so may cause a damage to the outdoor unit