11. Installation

Outdoor Units
• Construct a protection wall with a solid material such as concrete to block the sea breeze. Make sure that
the height and the width of the wall are 1.5 times larger than the size of the outdoor unit.
Also, secure a space larger than 27.6 inch(700mm) between the protection wall and the outdoor unit for
exhausted air to ventilate.
CAUTION
• Depending on the condition of the power supply, unstable power or voltage may cause malfunction of
parts or control system (example: on a boat or places using power supplied from electric generator, etc.).
• Install the unit in a place where water can drain smoothly.
• If you have any difficulty finding installation location as prescribed above, contact your manufacturer for
details.
• Consider that the salinity particles clinging to the external panels should be sufficiently washed out. Be
sure to clean sea water and dust from the outdoor unit heat exchanger and apply a corrosion inhibitor on
it at least once a year.
• Because the residual water at the bottom of the outdoor unit significantly promotes corrosion, make sure
that the slope does not disturb drainage.
− Keep the floor level so that rain does not accumulate.
− Be careful not to block the drain hole.
• Check the condition of the product periodically.
− Check the installation site every 3 months and perform anti-corrosion treatment such as commercial
water repellent grease and wax, etc., based on the product condition.
− When the product is to be shut down for a long period of time, off-season periods, take appropriate
measures like covering the product.
• If the product installed within 1640.4 ft (500 m) of seashore, special anti-corrosion treatment is required.
※ Please contact your local SAMSUNG representative for further details.