  • Page 1 Air conditioner Installation manual MN4DKH Thank you for purchasing this Samsung air conditioner. Before operating this unit, please read this manual carefully and retain it for future reference.
  • Page 2: Table Of Contents

    Contents Safety Information Installation Procedure Step 1 Checking and preparing accessories Step 2 Choosing the installation location Step 3 Optional: Insulating the body of the indoor unit Step 4 Installing the indoor unit Step 5 Purging inert gas from the indoor unit Step 6 Cutting and flaring the pipes Step 7 Connecting the assembly pipes to the refrigerant pipes Step 8 Performing the gas leak test...
  • Page 3: Safety Information

    Safety Information WARNING CAUTION WARNING General information WARNING Installing the unit WARNING IMPORTANT: When installing the unit, always remember to connect first the refrigerant tubes, then the electrical lines. English...
  • Page 4 Safety Information – – Step 13 Optional: Extending the power cable CAUTION Make sure that you earth the cables. Install the circuit breaker. Power supply line, fuse or circuit Make sure that the condensed water dripping from the drain hose runs out properly and safely. breaker Install the power cable and communication cable of the indoor and outdoor unit at least 1m away from the electric...
  • Page 5: Installation Procedure

    Installation Procedure Step 1 Checking and preparing Step 2 Choosing the installation accessories location Installation location requirements Pattern sheet (1) Drain hose (1) Insultaion pipe Insultaion drain hose (1) (Liquid side1, gas side1) Installation manual (1) User manual (1) Cable-tie (6) Clamp (1) English...
  • Page 6 Installation Procedure Indoor unit dimensions 890~910 (Celling opening) 735 (Celling opening) Sub duct connection Model Chassis Net dimension (W × D × H) Liquid pipe connection inch Gas pipe connection inch Drain hose connection English...
  • Page 7 Spacing requirements CAUTION 1500 mm or more 2500 mm or more 20 mm Obstruction Model C: 1500 mm or more English...
  • Page 8: Step 3 Optional: Insulating The Body Of The Indoor Unit

    Installation Procedure Step 3 Optional: Insulating the body Step 4 Installing the indoor unit of the indoor unit NOTE NOTE Concrete Hole in anchor Insert Indoor <S> Hole in plug unit 910X151 910X235 Suspension bolt (M8) - field supply 610X151 610X235 650X151 650X235...
  • Page 9: Step 5 Purging Inert Gas From The Indoor Unit

    Step 5 Purging inert gas from the CAUTION indoor unit Unscrew the pinch pipe at the end of each refrigerant pipe. Insulator Liquid side CAUTION Gas side NOTE 20 mm Indoor unit Ceiling 17 mm Gauge of dimensions English...
  • Page 10: Step 6 Cutting And Flaring The Pipes

    Installation Procedure Step 6 Cutting and flaring the pipes Pipe cutter Damaged Cracked Uneven Correct Inclined Thickness Surface 90° Step 7 Connecting the assembly pipes to the refrigerant pipes Pipe Oblique Rough Burr There are two refrigerant pipes of different diameters : R 0.4 to 0.8 mm Flare Pipe...
  • Page 11: Step 8 Performing The Gas Leak Test

    Step 8 Performing the gas leak test Outer Diameter (mm) NOTE Step 6 Cutting and flaring the pipes Insulator Liquid side Gas side Step 9 Insulating the refrigerant pipes CAUTION No gap NOTE English...
  • Page 12 Installation Procedure Insulation cover pipe Insulation pipe Indoor unit Be sure to overlap the insulation. Insulation type (heating/cooling) CAUTION Standard High humidity Pipe Pipe size Remarks (Less than 30°C, (Over 30°C, 85%) 85%) EPDM, NBR CAUTION <Geological condition> Hanger Additional insulation <Operation purpose condition>...
  • Page 13: Step 10 Installing The Drain Hose And Drain Pipe

    Step 10 Installing the drain hose and CAUTION drain pipe Air ventilation Ceiling 20 mm or more Drain hose Band joint 1/100 or more 550 mm 300 mm or less or less Ceiling Drain socket Metal clamp Drain hose Drain pipe Under gradient Be sure to bond the drain Large seailng pad...
  • Page 14 Installation Procedure Support pieces 1 to 1.5 m Indoor unit 1/100 or more Max. 20 mm Ceiling Be horizontal Indoor unit Max. 30˚ Indoor unit Flexible hose NOTE Hanger 1~1.5m Main air vent Individual air vent 550mm or less Main drainpipe Centralized horizontal drainpipe (more than 1/100 slope) English...
  • Page 15: Step 11 Performing The Drainage Test

    Step 11 Performing the drainage test CAUTION Water leakage check part Flexible hose CAUTION Hose CAUTION English...
  • Page 16: Step 12 Connecting The Power And Communication Cables

    Installation Procedure Step 12 Connecting the power and 1 phase communication cables CAUTION Indoor Unit 1(L) 2(N) Outdoor Unit 1(L) 2(N) CAUTION Cable Cable clamp Indoor Power Main power cable Communication cable Indoor power supply Power supply Max/Min(V) Indoor power cable ±10% 50/60Hz Communication cable...
  • Page 17: Step 13 Optional: Extending The Power Cable

    Step 13 Optional: Extending the power cable Tools Spec Shape CAUTION CAUTION Power cable (Unit: mm) Pre-installed tube for the power cable (Unit: mm) English...
  • Page 18 Installation Procedure Contraction tube Method 1 Method 2 Method 1 Method 2 Insulation tape Connection sleeve Connection sleeve CAUTION Compression dimension WARNING Method 1 Method 2 – Compress it 4 times. Compress it 4 times. 5 mm 5 mm Method 1 Method 2 Insulation tape Insulation tape...
  • Page 19 Step 14 Setting the indoor unit addresses and the installation options CAUTION Common steps for setting the addresses and options MR-EC00 and MR-EH00 remote controls Entering the Setting the mode for setting option values the options SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7...
  • Page 20 Installation Procedure Steps Remote control display Cool English...
  • Page 21 Steps Remote control display Heat Auto English...
  • Page 22 Installation Procedure Steps Remote control display Cool English...
  • Page 23 Steps Remote control display Heat [SEG2, SEG3] [SEG4, SEG5] [SEG6, SEG8] [SEG9, SEG10] 0 0 [SEG11, SEG12] [SEG14, SEG15] [SEG16, SEG17] 7 7 [SEG18, SEG20] 0 0 [SEG21, SEG22] [SEG23, SEG24] 4 4 English...
  • Page 24 Installation Procedure Setting the indoor unit addresses Option No. for an indoor unit address: 0AXXXX-1XXXXX-2XXXXX-3XXXXX Indoor Unit Common steps for setting the addresses and options Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 English...
  • Page 25 CAUTION Setting the installation options in a batch Option No. for an indoor unit address: 02XXXX-1XXXXX-2XXXXX-3XXXXX Indoor Unit Common steps for setting the addresses and options Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 English...
  • Page 26 Installation Procedure Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 Option SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 English...
  • Page 27 Condition SEG14 Setting Result External control Level control Indoor 1 Indoor 2 Indoor 3 Indoor 4 Changing the addresses and options individually Common steps for setting the addresses and options Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Option SEG1 SEG2 SEG3 SEG4 SEG5...
  • Page 28: Optional: Installing Dpm (Digital Packaged Multi)

    Installation Procedure Optional: Installing DPM (Digital Packaged Multi) NOTE CAUTION English...
  • Page 29: Troubleshooting

    Troubleshooting Troubleshooting LED lamp display Operation Defrost Timer Filter Abnormal conditions Remarks English...