List of parameters PME71.901...

The following pages have the Menus and the list of parameters
for setting up the LCD AZL 2... Display for the LME 71... control
box with PME 71.901...
Parameter
Nr.
Description
000
Internal parameter
41
Password for heating engineering (4 characters) Modification
42
Password OEM (5 characters)
60
Backup/Restore
100
General notes
102
Identification date
103
Identification number
113
Burner identification
123
Step control min output.
Displaying the unit operation mode and display-
ing AZL2...
1 = standard (program phase)
140
2 = flame 1 (QRA.../ION)
3 = flame 2 (QRB.../QRC...) ® not used
4 = output active (output value)
164
Number of resettable start-ups
166
Total number of start-ups
170.00
Switching cycles relay contact K12
170.01
Switching cycles relay contact K11
170.02
Switching cycles relay contact K2
170.03
Switching cycles relay contact K1
171
Max. relay commutation cycles
200
Burner Control
224
Air pressure switch special time
225
Pre-purging time - 2.1 seconds
226
Spark pre-ignition time
Interval: End of the safety time - resetting of the
230
load regulator
234
Post-purging time
Air pressure switch input
235
0 = inactive
1 = active
Repetitions meter
240.00
Limit value of flame loss during operation
Repetitions meter
240.01
Limit value of No flame at the end of the safety
time
Valves Seal Control
241.00
0 = OFF
1 = ON
Valves Seal Control
241.01
0 = during pre-purging
1 = during post-purging
Valves Seal Control
241.02
0 = according to P241.01
1 = during pre-purging and post-purging
242
Evacuation of valve seal control test area
Atmospheric pressure valve seal control time
243
test
244
Filling the valve seal control test area
245
Gas pressure valve seal control time test
257
Post-ignition time -0,3 seconds
400
Ratio control (operation)
403.00
Fan speed: Ignition load speed (P0)
403.01
Fan speed: Low flame speed (P1)
403.02
Fan speed: High flame speed (P2)
500
Ratio control
503.00
Speed without PWM fan flame: Standby speed
List of parameters PME71.901...
The values shown in the "Factory setting" column, in the table be-
low, are only given as a guide (Control box not programmed).
Values interval
Modification
Min.
xxxx
Modification
xxxxx
Modification
Restore
Reading only
---
Reading only
0
Modification
x
Modification
1%
Modification
1
Resettable
0
Reading only
0
Reading only
0
Reading only
0
Reading only
0
Reading only
0
Reading only
0
Modification
0s
Modification
0s
Modification
1.029 s
Modification
3.234 s
Modification
0s
Modification
0
Modification
0
Modification
0
Modification
0
Modification
0
Modification
0
Modification
0s
Modification
1.029 s
Modification
0s
Modification
1.029 s
Modification
0s
Modification
800 rpm
Modification
800 rpm
Modification
800 rpm
Modification
0 rpm
65
GB
Factory
Resolution
setting
Max.
xxxx
---
xxxxx
---
Backup
---
---
---
9999
1
xxxxxxxx
1
burnErId
10%
0.1
4
1
999999
1
999999
1
999999
1
999999
1
999999
1
999999
1
999999
1
13.818 s
0.294 s
13.818 s
1237 s
4.851 s
29.106 s
37.485 s
0.147 s
6.174 s
74.97 s
0.294 s
9.408 s
1237 s
4.851 s
19.404 s
1
1
2
1
1
1
1
1
1
1
1
1
2.648 s
0.147 s
2.648 s
37.485 s
0.147 s
10.290 s
2.648 s
0.147 s
2.648 s
37.485 s
0.147 s
10.290 s
13.23 s
0.147 s
2.205 s
900 rpm
10 rpm
3000 rpm
900 rpm
10 rpm
1200 rpm
900 rpm
10 rpm
5700 rpm
9000 rpm
10 rpm
Password
Password
reading
writing level
level to
to level
level
---
---
OEM
---
---
OEM
---
---
SO
---
Info
---
0
Info
---
Info
SO
2
SO
SO
4
SO
SO
0
Info
Info
0
Info
---
0
Info
---
0
Info
---
0
Info
---
0
Info
---
0
Info
---
SO
OEM
SO
OEM
SO
OEM
SO
OEM
SO
OEM
0
SO
OEM
0
SO
OEM
1
SO
OEM
1
SO
OEM
1
SO
OEM
0
SO
OEM
SO
OEM
SO
OEM
SO
OEM
SO
OEM
SO
OEM
SO
SO
SO
SO
SO
SO
0 rpm
SO
SO
20152192

Advertisement

Table of Contents
loading

Table of Contents