Burner Adjustment; Indicative Calibration Values; Switching Off The Burner; Load Controller Inputs - Riello 20148874 Installation, Use And Maintenance Instructions

Premix gas burners
Table of Contents

Advertisement

7.7

Burner adjustment

The optimum adjustment of the burner requires an analysis of
flue gases at the generator outlet.
The burner application at the generator, the adjustment and the
testing must be carried out in compliance with the instruction
manual of the generator itself, including the control of the concen-
tration of CO and CO
in the flue gases and of their temperature.
2
Check in sequence:
MAX output
MIN output
The MAX output should be equal to the value requested by the
boiler used. To increase or decrease its value use the external
modulation control.
Measure the gas delivery on the counter to precisely establish the
burnt output.
Using a smoke analyser, measure the value of the CO
in order to optimise the burner calibration.
The correct values are: CO
To correct these values act on the gas valve in the following way:
 to increase the gas delivery and the CO
towards the "+" sign (Fig. 165);
 to reduce the gas delivery and the CO
towards the "-" sign (Fig. 165);.
The MIN output should be equal to the value requested by the
boiler used. To increase or decrease its value use the external
modulation control.
Measure the gas delivery on the counter to precisely establish the
burnt output (to be adjusted depending on gas pressure).
Using a smoke analyser, measure the value of the CO
in order to optimise the burner calibration.
The correct values are: CO
To correct these values act on the gas valve in the following way:
 to increase the gas delivery and the CO
towards the "+" sign;
 to reduce the gas delivery and the CO
towards the "-" sign;.
7.8

Switching off the burner

Turn the "ON/OFF" switch to "OFF" (Fig. 164 on page 51).
Disable the electrical supply. If the burner is off for long periods,
close the manual gas gates.
7.9

Load controller inputs

Selecting the default output analogue source/phases input
with 3 positions (P654)
The following input signals can be selected and managed using
the parameter P654.
3 positions phase input (ASZxx.3x feedback potentiometer
necessary/depending on the sequence of the program)
0...10 V
0...135 
0...20mA
4...20 mA with lockout at I <4 mA (AZL2...: Loc: 60)
20152192
Start-up, calibration and operation of the burner
2
8.2 - 9% (for methane).
2
: turn the V1 screw
2
: turn the V1 screw
2
2
7.8 - 8.5% (for methane).
2
: turn the V2 screw
2
: turn the V2 screw
2
20076453
3
or the O
2
Key (Fig. 165)
1
Maximum gas flow adjustment (V1)
2
Pressure point downstream
3
Minimum gas flow adjustment (V2)
7.7.1

Indicative calibration values

Methane
LPG
G25
or the O
2
D9714
WARNING
NOTE:
For the connections, see the wiring diagrams.
54
GB
2
1
MIN output
CO
(%)
O
(%)
CO
2
2
8
6.6
9.5
6.4
7.8
6.8
Turning the "ON/OFF" switch to "OFF" position
during the burner post-ventilation phase, the
equipment shuts down after a few seconds (ER-
ROR LOC:83).
Fig. 165
MAX output
(%)
O
(%)
2
2
8.5
5.7
10
5.6
8.3
5.8
Tab. Q
Fig. 166