Output supplied

The diagrams allow you to set the power output either using the
number of fan revs or using the pressure downstream of the gas
valve (Fig. 22 on page 24).
Example RX 700 S/PV:
natural gas G20 PCI 9.45 kWh/Sm
pressure on point 1 = - 12 mbar (2nd chart)
burnt output corresponds to 600 kW
Going vertically up the 1st diagram, to intersect the dotted line,
you can estimate the value of the number of revs on the left hand
y-axis: in this case 3800 rpm.
For an exact reading of the number of revs there is a kit for inter-
facing with the control box.
NOTE:
the burner can operate with LPG without any additional kit, how-
ever a different regulation of the gas valve is required.
For the G25 the supplied mixer ring for the G25 needs to be ap-
plied as shown in Fig. 8 on page 14.
* For the RX 850 S/PV version, add the mixer ring to the one al-
ready installed on the burner as standard.
Model
RX 700 S/PV
RX 850 S/PV
RX 1000 S/PV
RX 700 S/PV



























Technical description of the burner
3
Ring (mm)
5
7 *
17
DOC-0078539
Thermal power – kW
LPG
RX 850 S/PV


















Tab. F



RX 1000 S/PV













G25





G20







Fig. 4





13
GB
Thermal power – kW
Thermal power – kW
G25
DOC-0078538
G20
G25
LPG
Fig. 5
DOC-0078537
G20
LPG
Fig. 6
20152192