Layout And Example Connections - ABB ACS580-04 Hardware Manual

Drive modules
Hide thumbs Also See for ACS580-04:
Table of Contents

Advertisement

220 CMOD-01 multifunction extension module (external 24 V AC/DC and digital I/O)

Layout and example connections

5
4
1
Grounding screw
2
Hole for mounting screw
2-pin terminal block for external power supply (5)
24 V AC/DC
40
24 V AC/DC + in
41
24 V AC/DC - in
3-pin terminal block for for transistor output (4)
24 V DC
42
DO1 SRC
43
DO1 OUT
44
DO1 SGND
1) Digital output connection example
2) An externally supplied frequency indicator which provides, for example:
• a 40 mA / 12 V DC power supply for the sensor circuit (CMOD frequency output)
• suitable voltage pulse input (10 Hz ... 16 kHz).
1
+
24V AC/DC + in
40
-
41
24V AC/DC - in
External 24 V (AC/DC) input
External 24 V (AC/DC) input
DO1 SRC
42
DO1 OUT
43
DO1 SGND
44
1)
42
DO1 SRC
43
DO1 OUT
DO1 SGND
44
2)
Source input
Digital or frequency output
Ground (earth) potential
3
6
3
2
6
Diagnostic LED
3-pin terminal blocks for relay outputs (3)
24 V DC
50
RO4C
Common, C
51
RO4A
Normally closed, NC
52
RO4B
Normally open, NO
53
RO5C
Common, C
54
RO5A
Normally closed, NC
55
RO5B
Normally open, NO
RO4C
50
RO4A
51
RO4B
52

Advertisement