364 Optional I/O extension modules
Isolation areas:
1
2
Dimension drawing
Analog inputs (80...82, 83...85)
•
Wire size max. 1.5 mm
The dimensions are in millimeters and [inches].
•
Input voltage (AI+ and AI-): -10 V ... +10 V
•
Input resistance: > 200 kohm
•
Optional cable shield connection
Analog outputs (86...88, 89...91)
•
Wire size max. 1.5 mm
•
Output voltage (AO and AGND): 0 V ... 10 V
•
Output resistance: < 20 ohm
•
Recommended load: > 10 kohm
•
Inaccuracy: typical ± 1%, max. ± 1.5% of full scale
•
Optional cable shield connection
Analog output scale switch
•
ON state: 0.5 V ... 9.5 V range in use
•
OFF state: 0 V ... 10 V range in use
1
AO3
2
AI4
Symbol
Description
Plugged to drive control unit SLOT2
1
Plugged to drive SLOT2
Switch
2
SWITCH
Reinforced insulation (IEC 61800-5-1:2007)
Reinforced insulation (IEC 61800-5-1:2007)
Functional insulation (IEC 61800-5-1:2007)
Functional insulation (IEC 61800-5-1:2007)
2
2
CBAI-01 bipolar analog IO adapter module 211
CBAI-01
AO4
AI4