1MRK 511 409-UEN D
Section 11
11.1

Testing disturbance report

11.1.1

Introduction

The following sub-functions are included in the disturbance report function:
Disturbance recorder
Event list
Event recorder
Trip value recorder
Indications
If the disturbance report is set on, then its sub-functions are also set up and so it is not
possible to only switch these sub-functions off. The disturbance report function is switched
off (parameter
Settings/Monitoring/Disturbance report/DRPRDRE:1.
11.1.2

Disturbance report settings

When the IED is in test mode, the disturbance report can be made active or inactive. If the
disturbance recorder is turned on during test mode, recordings will be made. When test mode
is switched off all recordings made during the test session are cleared.
Setting
on the local HMI under Main menu/Settings/IED Settings/Monitoring/Disturbance report/
DRPRDRE:1.
11.1.3

Disturbance recorder (DR)

Manual Trig can be started at any time. This results in a recording of the actual values from
A
all recorded channels.
Manual Trig can be started in two ways:
The
1.
From the local HMI under Main menu/Disturbance records.
1.1.
1.2.
2.
Open the Disturbance handling tool for the IED in the plant structure in PCM600.
2.1.
2.2.
2.3.
2.4. Right-click and select
Phasor measurement unit RES670
Commissioning manual
Testing functionality by secondary
injection
Operation = Off ) in PCM600 or the local HMI under Main menu/Settings/IED
OpModeTest for the control of the disturbance recorder during test mode are located
Enter on the row at the bottom of the HMI called Manual trig.
A new recording begins. The view is updated if you leave the menu and return.
Navigate to General information or to Trip values to obtain more detailed
information.
Right-click and select
Read the required recordings from the IED.
Recordings and select a recording.
Refresh the window
disturbance analyzing tool that can handle Comtrade formatted files.
Execute manual Trig in the window Available recordings in IED .
Create Report or Open With to export the recordings to any
Testing functionality by secondary injection
Section 11
M17101-2 v7
M11746-2 v7
M11750-2 v7
79