Overview Of System Protocol For Mindconnect Nano - Siemens MindConnect Nano System Manual

Insights hub
Hide thumbs Also See for MindConnect Nano:
Table of Contents

Advertisement

Quantity
Response address offset
Response quantity
1)
Sample start offset as documented in SENTRON PAC manual - can be used without
decrementing it by 1.
Technical specification
Protocol
Modbus RTU - RS485
Modbus RTU - RS422
Modbus RTU - RS232

4.6 Overview of SYSTEM protocol for MindConnect Nano

You can use the protocol SYSTEM to implement a system information adapter for analysis
purposes. The SYSTEM protocol can collect the following information from MindConnect Nano:
Overall CPU load
Overall memory consumption
Network traffic
Application specific data
CPU load memory consumption
Disk usage
71
Using decremented
start address
1
0
1
Description
Data provider
Max cable length
Data provider
Max cable length
Data provider
Maximum cable length
4.6 Overview of SYSTEM protocol for MindConnect Nano
Using address
Getting data from a read
from manual
data block
1
27
-1
11
1
16
Value
Data rate
32
1200 m
max. 115,2 kBd
10
1200 m
max. 115,2 kBd
1
900 m
2,4 kBd
300 m
4,8 kBd
152 m
9,6 kBd
15 m
19,2 kBd
5 m
57,6 kBd
< 2 m
115,2 kBd