4.11.8 Remote output selection (REM signal, Pr. 495 to Pr. 497)

You can utilize the ON/OFF of the inverter's output signals instead of the remote output terminal of the programmable
logic controller.
Parameter
Name
Number
Remote output
495
selection
496∗
Remote output data 1
497∗
Remote output data 2
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 187)
∗ This parameter allows its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter write selection.
<Remote output data>
Pr. 496
b11
Pr. 497
b11
∗1
Any
∗2
Y0 to Y6 are available only when the extension output option (FR-A7AY E
kit) is fitted
∗3
RA1 to RA3 are available only when the relay output option (FR-A7AR E
kit) is fitted
Example: When "96 (positive logic)" is set in Pr. 190 RUN terminal function selection and "1" (H01) is set in Pr. 496, the
terminal RUN turns ON.
ON/OFF example for positive logic
Pr. 495 = 0, 10
Power
Power
OFF
supply
supply
REM
OFF
REM signal clear
Signal condition during a reset
Pr. 495 = 0, 1
Reset
ON
Reset
REM
ON
OFF
∗ When Pr. 495 = "1," the signal condition saved in EEPROM (condition of the
last power OFF) is applied.
REMARKS
The output terminal where the REM signal is not assigned using any of Pr. 190 to Pr. 192 does not turn ON/OFF if 0/1 is set to
the terminal bit of Pr. 496 or Pr. 497. (It turns ON/OFF with the assigned function.)
Parameters referred to
Pr. 190 to Pr. 192 (output terminal function selection)
Function assignment of external terminal and control
Initial
Setting
Value
Range
0
1
0
10
11
0
0 to 4095
0
0 to 4095
b0
b0
Pr. 495 = 1, 11
OFF
Inverter
reset time
(about 1s)
REM
ON
REM signal held
REM signal is saved
Pr. 495 = 10, 11
ON
REM
ON
Remote output data clear at powering OFF
Remote output data retention at powering
OFF
Remote output data clear at powering OFF
Remote output data retention at powering
OFF
Refer to the following diagram.
The output terminal can be turned ON/OFF depending on
the Pr. 496 or Pr. 497 setting. The remote output selection
can
be
controlled
communication
from
communication from the communication option.
Set "96 (positive logic) or 196 (negative logic)" to any of
Pr. 190 to Pr. 192 (output terminal function selection), and
assign the remote output (REM) signal to the terminal
used for remote output,
When you refer to the diagram on the left and set 1 to the
terminal bit (terminal where the REM signal has been
assigned) of Pr. 496 or Pr. 497, the output terminal turns
ON (OFF for negative logic). By setting 0, the output
terminal turns OFF (ON for negative logic).
When Pr. 495 = "0 (initial value), 10", performing a power ON
reset (including a power failure) clears the REM signal
output. (The ON/OFF status of the terminals are as set in Pr.
190 to Pr. 192. ) The Pr. 496 and Pr. 497 settings are also "0".
When Pr. 495 = "1, 11", the remote output data before power
OFF is stored into the EEPROM, so the signal output at
power recovery is the same as before power OFF. (See the
chart on the left) However, it is not stored when the inverter
is
reset
(terminal
communication).
When Pr. 495 = "10 or 11," the signal before the reset is held
even during an inverter reset.
Refer to page 144
Description
Remote output data is
cleared during an
inverter reset
Remote output data is
retained during an
inverter reset
ON/OFF
by
computer
the
PU
connector
reset,
reset
request
link
or
by
4
through
151