Hide thumbs Also See for FPS300.245-049-112:

Advertisement

Quick Links

G
ENERAL DESCRIPTION
The FPS300 is an industrial grade power supply for the
1-phase mains system, it is incorporated into a rugged
wall-mount housing with an
protection.
It provides two to four stabilized outputs that are
galvanically separated from the input. The negative
potential of the outputs is permanently connected to
PE within the unit.
The most outstanding features of the FPS series are the
compact size, the wide operating temperature range,
the extremely low input inrush current and the very
high efficiencies, which are achieved through various
design technologies. Large output capacitors can
absorb and store regenerative energy from breaking
motors.
High immunity to transients and power surges as well as
low electromagnetic emissions and an international
approval package make it possible for nearly every
application. The various connector options support the
different needs of individual applications. Please contact
PULS for possible options.
O
RDER NUMBERS
Description:
Order Number
FPS300.245-049-112*
Accessories:
Related Products
*For DIN rail mounting PSU: (Order Number)D
e.g. FP300.245-049-112D
All parameters are specified at 24V, 12.5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
Aug. 2023 / Rev. 1.0 DS- FPS300.245-049-112-EN
IP65/67 degree of
Power supply FPS300
Input
Output
7/8" 3pin
7/8" 4pin
Chapter 21
Chapter 22
P
OWER SUPPLY
IP 65/67 Degree of protection
600 W
5 s
peak
AC 100-240 V wide-range input
3 switchable outputs
Outputs for actors and sensors share one channel
95.7 % full load and excellent partial load efficiencies
DIN rail mounting possible, option "D"
Output connected to PE (PELV)
Version without connection to PE on request
Large output capacitors
Not potted
Negligible low input inrush current surge
Full power between -25 °C and +55 °C
IO-Link
3 years warranty
S
HORT-FORM DATA
Output voltage
DC 24 V
Adjustment range
24-28 V
Output power
Continuous:
360 / 300 / 150 W +45 / +55 / +70 °C
Short term up to 5 s
600 / 300 W
Derate linearly
+55 °C to +70 °C
Number of output
3
Output currents
Settable per output; up to 10 A
Input voltage AC
AC 100-240 V
Input voltage DC
DC 110-300
Power factor
0.99 / 0.97
AC Inrush current
2.6 / 6 A
Efficiency
94.3 / 95.7 %
Losses
18.1 / 13.5 W
Hold-up time
44 / 44 ms
Temperature range
-25 °C to +70 °C
Size (wxhxd)
181x183x59 mm Without connectors
Weight
1200 g / 2.7 lb
*)
For DC supply voltages above 150 Vdc an external fuse is
required.
M
AJOR APPROVALS AND CONFORMITY
For details or a complete approval list, see chapter 21.
IEC 62368-1
IEC 61010-2-201
www.pulspower.com
FPS300.245-049-112
100-240Vac 24V 300W
Nominal
Factory setting 24.5 V
Up to:
+55 / +70 °C
-15 / +10 %
V*)
±20 %
At 120 / 230 Vac
At 120 / 230 Vac
peak
At 120 / 230 Vac
At 120 / 230 Vac
At 120 / 230 Vac
1 / 40

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FPS300.245-049-112 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Puls FPS300.245-049-112

  • Page 1 *For DIN rail mounting PSU: (Order Number)D e.g. FP300.245-049-112D All parameters are specified at 24V, 12.5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 DS- FPS300.245-049-112-EN www.pulspower.com 1 / 40...
  • Page 2: Table Of Contents

    A key word indicating flexibility of choice with a strongly preferred implementation. Sensor output Actor output All parameters are specified at 24V, 12.5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 DS- FPS300.245-049-112-EN www.pulspower.com 2 / 40...
  • Page 3 Terminal configuration e.g. .002. Input: HanQ4/2 Com: M12-A Output: HanQ4/0 Consecutively numbered All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com 3 / 40...
  • Page 4: Intended Use

    This must be suitably located and easily accessible. The disconnecting means must be marked as the such for the device. All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com 4 / 40...
  • Page 5: Ac-Input

    Power factor vs. output power at 24 V output voltage voltage All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com 5 / 40...
  • Page 6: Dc-Input

    Fig. 5-1: Typical turn-on behavior at nominal load and 25 °C ambient temperature All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com...
  • Page 7: Output

    For all four outputs in total All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com 7 / 40...
  • Page 8 Fig. 6-3: Trip curve diagram All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com 8 / 40...
  • Page 9: Hold-Up Time

    Fig. 7-1: Hold-up time vs. input voltage Fig. 7-2: Shut-down behavior, definitions All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com 9 / 40...
  • Page 10: Io-Link Interface

    To operate the IO-Link interface it is required to install/upload the IODD-File (IO-Link Device Description) into the connected IO-Link master. The most recent IODD file can be found on the PULS website (www.pulspower.com) in the download section of the individual product page. The device can also be accessed via IO-Link, if the power supply is not connected to AC- mains and in a switched off mode.
  • Page 11 0-49 V Actual average output voltage All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com 11 / 40...
  • Page 12 Overall performance of the PSU might decrease at low remaining endurance. All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com 12 / 40...
  • Page 13 Octet 2,3 - EventCode Item [4] Item [5] All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com 13 / 40...
  • Page 14 Pre-alarm channel 1 to pre-alarm limit channel 4 All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com 14 / 40...
  • Page 15 For a full list of data set, see chapter 24, IO-Link Data Typs and Description. All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com...
  • Page 16: Efficiency And Power Losses

    Losses vs. input voltage at 24 V, 300 W, typ. All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com...
  • Page 17: Lifetime Expectancy

    At 24 V, 300 W and 25 °C; Ground Fixed GF25 All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com...
  • Page 18: Functional Diagram

    Functional Diagram Fig. 12-1: Functional Diagram All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com 18 / 40...
  • Page 19: Dimensions And Connector Variants

    Pin 4: GND Ua Actor output All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com 19 / 40...
  • Page 20: User Interface

    Return to the Output Power Mode/default mode by pushing beyond the highest (OUT4) or lowest (OUT1) output number. All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com 20 / 40...
  • Page 21 Status LED turns to solid green again. All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com...
  • Page 22  for more than 5 s All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com 22 / 40...
  • Page 23: Emc

    For IO Link certification immunity test levels according EN 61326-1:2013-01 have been tested All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com...
  • Page 24 48 Mhz and 32 MHz Fixed frequency All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com 24 / 40...
  • Page 25: Environment

    Fig. 16-2: Output power vs. altitude All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com 25 / 40...
  • Page 26: Safety And Protection Features

    0.51 mA At 264Vac, 60Hz All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com 26 / 40...
  • Page 27: Dielectric Strength

    IO-Link Fig. 18-1: Dielectric strength All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com 27 / 40...
  • Page 28: Approvals And Fulfilled Standards

    Safety Isolating Transformers corresponding to Part 2-6 of the IEC/EN (Annex BB) Transformer 61558 All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com 28 / 40...
  • Page 29: Accessories

    FIEPOS features a large number of different connectors. In some cases mating connectors and/or cord assemblies can be ordered from PULS. Ask your PULS representative if available. All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted.
  • Page 30: Application Notes

    All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com...
  • Page 31: Mounting Orientations

    Over-head and Supply Supply Table-top mounting All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2023 / Rev. 1.0 FPS300.245-049-112-EN www.pulspower.com 31 / 40...
  • Page 32: Io-Link Data Types And Description

    FPS300.245-049-112 IO-Link Data Types and Description 23.1. Cyclic Data The first dataset is called process data and refers to data that is periodically sent to the IO-Link master. The data is updated and communicated every 2ms. All other data in the power supply itself is generated every 50ms and stored in the IO-Link registers.
  • Page 33 FPS300.245-049-112 Octet Subindex Bit offset 119-112 111-104 103-96 95-88 87-80 79-72 71-64 63-56 55-48 47-40 Octet 12 Subindex Bit offset Octet13 Subindex Bit offset Octet14 Subindex Bit offset All parameters are specified at 24 V, 20 A, 400 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted.
  • Page 34: Acyclic Data

    FPS300.245-049-112 23.2. Acyclic data The parameter values can be accessed to read out additional data (e.g. current output voltage, temperatures etc.), but in addition some of these values can also be written by the user to configure the power supply (e.g. output voltage and remote on/off).
  • Page 35 FPS300.245-049-112 Parameter Para. Sub- Data Read [R] Description Index index offset type length Write [W] PSU events uint16 dynamic Output-OK bool bit 0…Output Voltage >90% of adjusted output voltage DC-Warning bool bit 1… Output voltage dips more than 10% below adjusted output voltage...
  • Page 36 FPS300.245-049-112 Parameter Para. Sub- Data Data Resolution Default Read [R] Allowed values Description Index index type offset Format values Write [W] Temperature secondary inside 69 int16 15-0 Q9.7 °C/bit -5120…32640 Temperature secondary inside PSU -40 .. 150°C max. temperature secondary Maximum temperature secondary inside PSU -40 ..
  • Page 37 FPS300.245-049-112 Parameter Para. Sub- Data Data Resolution Default Read [R] Allowed values Description Index index type offset Format values Write [W] 0 … “<=10%” 1 … “>10%” Remaining Endurance LED uint8 2 … “>=25%” Dynamic coded 3 … “>=50%” 4 … “>=75%”...
  • Page 38 FPS300.245-049-112 Counter Parameter Para. Sub- Data type Data Resolution Default Read [R] Allowed values Description Index index offset Format value Write [W] E-Fuse Number of Startups all CHs uint32 array 95-0 0…150000 Number of Startups all Channels E-Fuse Number of Startups CH1...
  • Page 39 FPS300.245-049-112 Device Status Parameter Para. Sub- Data type Read [R] Allowed values Description Index index offset Write [W] 0…Device is operating properly 0…Device is operating properly 1…Maintenance-Required 1…Maintenance-Required Device Status uint8 2…Out-of-Specification 2…Out-of-Specification 3…Functional-Check 3…Functional-Check 4…Failure 4…Failure Detailed Device Status...
  • Page 40: Events

    FPS300.245-049-112 23.3. Events This information is triggered by certain situations and will result in an event notification to the IO-Link master. Typical events are notification in case of ideal (e.g. DC-OK) and non- ideal situations (e.g. ambient temperature too hot, high input voltage etc.).

This manual is also suitable for:

Fiepos fps300

Table of Contents