Capacity Compensation Rate For Pipe Length And Height Difference; Models: Aoug09Lzah1 And Aoug12Lzah1 - Fujitsu AOUG09LZAH1 Design & Technical Manual

Hide thumbs Also See for AOUG09LZAH1:
Table of Contents

Advertisement

6. Capacity compensation rate for pipe length and height
difference
Indoor unit is higher than outdoor unit
Indoor unit
Connection pipe

6-1. Models: AOUG09LZAH1 and AOUG12LZAH1

NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Indoor unit is higher than outdoor
unit *1
Indoor unit is lower than outdoor
unit *2
HEATING
Indoor unit is higher than outdoor
unit *1
Indoor unit is lower than outdoor
unit *2
6-1. Models: AOUG09LZAH1 and AOUG12LZAH1
Height difference H
1
*
H
Outdoor unit
m
ft
15
49
10
33
7.5
25
5
16
0
0
-5
-16
-7.5
-25
-10
-33
-15
-49
m
ft
15
49
10
33
7.5
25
5
16
0
0
-5
-16
-7.5
-25
-10
-33
-15
-49
- 61 -
Indoor unit is lower than outdoor unit
Outdoor unit
H
Indoor unit
Connection pipe
Pipe length
5
7.5
10
16
25
33
-
-
-
-
-
0.956
-
0.988
0.960
1.017
0.992
0.964
1.025
1.000
0.971
1.025
1.000
0.971
-
1.000
0.971
-
-
0.971
-
-
-
Pipe length
5
7.5
10
16
25
33
-
-
-
-
-
0.981
-
1.000
0.981
1.017
1.000
0.981
1.017
1.000
0.981
1.012
0.995
0.976
-
0.993
0.974
-
-
0.971
-
-
-

6. Capacity compensation rate for pipe length and height difference

2
*
15
20
49
66
0.877
0.874
0.891
0.888
0.895
0.892
0.899
0.895
0.906
0.902
0.906
0.902
0.906
0.902
0.906
0.902
0.906
0.902
15
20
49
66
0.933
0.925
0.933
0.925
0.933
0.925
0.933
0.925
0.933
0.925
0.928
0.920
0.926
0.918
0.923
0.916
0.914
0.906