TWO-PIPE CASSETTE
FAN COIL UNIT
INSTALLATION MANUAL
SF-xxxC2M
SF-xxxC4M
AIR CONDITIONING

Advertisement

Table of Contents
loading

Summary of Contents for Sinclair SF C2M Series

  • Page 1 TWO-PIPE CASSETTE FAN COIL UNIT INSTALLATION MANUAL SF-xxxC2M SF-xxxC4M AIR CONDITIONING...
  • Page 2 “Original instructions”   IMPORTANT NOTE: Read this manual ca r efully befo r e installing or operating your new air conditioning unit. Make sure to save this manual for future reference.
  • Page 3: Table Of Contents

    Install according to this installation instructions strictly. CONTENTS PAGE If installation is defective, it will cause water leakage, electrical shock and fire. PRECAUTIONS..................1 When installing the unit in a small room, take measures against to keep refrigerant concentration from exceeding INSTALLATION INFORMATION..............2 allowable safety limits in the event of refrigerant leakage.
  • Page 4: Installation Information

    2. INSTALLATION INFORMATION CAUTION Ground the air conditioner. To install properly, please read this "installation manual" at Do not connect the ground wire to gas or water pipes, first. lightning rod or a telephone ground wire.Incomplete grounding may result in electric shocks. The air conditioner must be installed by qualified persons.
  • Page 5: Attached Fittings

    4. FITTINGS 4.1 Attached fittings 4.1 Attached fittings Please check whether the following fittings are of full scope. If there are some spare fittings , please restore them carefully Four-way Cassette INSTALLATION FITTINGS Four-way Cassette NAME SHAPE (compact) 3. Installation paper board 4.
  • Page 6: Fan Coil Unit Installation

    Face the concave side of the installation hooks toward the 5. FAN COIL UNIT INSTALLATION expansible hooks. Determine the length of the installation hooks from the height of ceiling, then cut off the unnecessary part. 5.1 Installation place If the ceiling is extremely high, please determine the (refer to fig.5-1,fig.5-2,fig.5-3 and table 5-1 for specification.) length of the installation hook according to facts.
  • Page 7 FIGURES Four-way Cassette Tubing side Tubing side Drain side Drain side Drain side Drain side Water pipe joint Water pipe joint Connecting point of drain pipe Connecting point of drain pipe Ceiling Ceiling Ceiling Ceiling Panel Panel Panel Panel Outlet Outlet Outlet Outlet...
  • Page 8 Four-way Cassette Four-way Cassette FIGURES 2 FIGURES 2 (compact) (compact) Tubing side Tubing side Drain side Drain side Drain side Drain side Four-Pipe Four-Pipe Connecting point of drain pipe Connecting point of drain pipe Water pipe joint Water pipe joint Ceiling Ceiling Ceiling...
  • Page 9: Connect The Drain Pipe

    5.4 Install The Panel 6. CONNECT THE DRAIN PIPE CAUTION 6.1 Install the drain pipe of indoor unit Never put the panel face down on floor or against the wall, or on bulgy objects. 1) The drainpipe can use PVC pipe (external diameter about 37 39mm, inner diameter is 32mm).
  • Page 10: Wiring

    0.8 1.0 m 0.8 1.0 m Gradient: Gradient: higher than 1/100 higher than 1/100 5 Turn off the power, drain the water away. The drain plug is used to empty the water-receiver for maintenance of the air conditioner. Please stuff it imposition at all times during operation to avoid leakage.
  • Page 11: Test Operation

    Table 7-1 510~2550 AIR FLOW(m 1-phase PHASE POWER FREQUENCY AND VOLT 220-240V~ 50Hz CIRCUIT BREAKER/FUSE(A) 15/15 BELOW 20M Twisted pairwire 2.5mm INDOOR UNIT POWER WIRING(mm BELOW 50M Twisted pairwire 6mm GROUND WIRING(mm The power cord type designation is H05RN-F or above. 8.