Examples:
EM300-SLD/ZLD:
Channel
Type
01
75
(Battery)
Channel
Type
68
04
(Humidity)
EM300-DI (Counter):
Channel
Type
01
75
(Battery)
Channel
Type
68
04
(Humidity)
5.3 Downlink Commands
EM300 series sensors support downlink commands to configure the device. The application
port is 85 by default.
Channel
03 (Set Reporting Interval)
ff
06(Set Threshold Alarm)
01 75 64 03 67 10 01 04 68 71 05 00 01
Value
Channel
64 => 100%
03
Value
Channel
71=>113
05
Hum=113*
0.5=56.5%
017564 03671e01 04685e 05c800000000
Value
Channel
64 => 100%
03
Value
Channel
5e=>94
05
Hum=94*
0.5=47%
Type
Type
67
10 01 => 01 10 = 272
(Temperat
Temp=272*0.1=27.2°C
ure)
Type
00
01=>Water is leaked
Type
67
1e 01 => 01 1e = 286
(Temperat
Temp=286*0.1=28.6°C
ure)
Type
c8
06 00 00 00=>
(Counter)
00 00 00 00=6
Description
2 Bytes, unit: s
9 Bytes, CTRL (1B) + Min (2B) +
Max (2B) +00000000(4B)
CTRL:
Bit0~Bit2:
000 - disable
001 - below (minimum threshold)
010 - above (maximum threshold)
www.ime.de
Value
Value
Value
Value
23