L 230V AC
N
N
L
B
2
A
1. Detach the plastic base (located in the bottom of the luminaire) by pulling the unlock hook and
pass the cables from area
connected to a permanent electrical installation to ensure the immobilization of the cable. Mount
the plastic base with the included mounting accessories.
2. Connect the mains cables to the respective detachable
terminal block. Ν for neutral, L for live wire.
3. Attach the luminaire by sliding it on the plastic base until the
plastic hook locks, and power the luminaire.
4. MAINTAINED/NON-MAINTAINED OPERATION
JUMPER SELECTION
You can choose the luminaire's operation. When the
jumper is installed (by default) in the middle and right pins
maintained operation is selected.
When the jumper is installed in the middle and left pins non-
maintained operation is selected.
NOTE!!
After finishing the installation you must power the device at least for 24 ours for battery
charging to perform the nominal autonomy.
Battery replacement
It can be done only by a competent person and after
the mains interruption.
1. Detach the luminaire from its base (step 1 of the
installation procedure).
2. Use a flat blade screwdriver to remove the diffusor.
3. Remove the reflector.
4. Disconnect the connector and remove the old battery.
5. Connect the new battery with the same type and
place it in the position of the old one.
6. Replace the removed parts (step 1,2 and 3).
Manufacturer
Model Number
Voltage Range
Nominal Power
Connections
Temperature (tc)
Page 2 of 3
INSTALLATION INSTRUCTIONS
Plastic base
Cable entry hole
or
and through the cable entry hole. The luminaire must be
A
B
LED MODULE CHARACTERISTICS
GR-108/12L/90
Cable connection between main pcb and led module
3
Non-maintained
operation
Olympia Electronics S.A.
0111163
2.9-3.6VDC
780mW
45 °C max. across the board
Lock - unlock hook
Maintained
operation
2
GR-109/12L/180
923109004_09_010