OPERATION MANUAL
Ultracool chillers
UC 2, UC 4, UC 8, UC 14, UC 24, UC 50, UC 65, UC 80, UC 100
DMI-0217-12
24/11/2022
Read this manual prior to performing any task!

Advertisement

Table of Contents
loading

Summary of Contents for Lauda UC 2

  • Page 1 OPERATION MANUAL Ultracool chillers UC 2, UC 4, UC 8, UC 14, UC 24, UC 50, UC 65, UC 80, UC 100 DMI-0217-12 24/11/2022 Read this manual prior to performing any task!
  • Page 2 LAUDA Ultracool S.L. personnel, or personnel authorized by LAUDA Ultracool S.L., should carry out any work in the refrigerating or electric circuit during the warranty period. After the warranty period, the work must be carried out by qualified personnel.
  • Page 3: Table Of Contents

    Site ................................6 Ultracool unit description ............................8 Setup of the Ultracool unit (UC 2 and UC 4) ..................8 Setup of the Ultracool unit (UC 8 to UC 65) ..................10 Setup of the Ultracool unit (UC 80 and UC 100) ................12 Identification labels on the Ultracool unit ....................
  • Page 4 Log Book .............................. 52 Annexes .................................. 53 11.1 Water quality ............................53 EC Declaration of Conformity UC 2 and UC 4 ....................54 EC Declaration of Conformity UC 8 to UC 100 ..................... 55 Attention. Points of special interest to keep in mind.
  • Page 5: Introduction

    INTRODUCTION 1.1 GENERAL NOTES • This water chiller complies fully with CE. • The Company does not accept responsibility if safety regulations are not met during handling, operation, maintenance and repair, even though these may not be strictly stated in this operation manual. •...
  • Page 6: Unpacking

    The chiller must be installed on a solid level surface that is capable of supporting a minimum of 150 kg (330 lb) for UC 2 and UC 4 models, 300 kg (660 lb) for UC 8 to UC 24 models, 650 kg (1430 lb) for UC 50 and UC 65 models and 850 kg (1875 lb) for UC 80 and UC 100 models.
  • Page 7 Ultracool unit from rain with a roof. Leave a space of 0,5m (20”) around the chiller for UC 2 and UC 4 models, 1m (40”) for UC 8 to UC 24 models and 2m (80”) for the UC 50 to UC 100 models. This space is important to facilitate maintenance work and cleaning, especially in front of the condenser (the heat exchanger on the back side of UC 2 and UC 4 models, the left side of UC 8 to UC 65 models and both left and right sides of UC 80 and UC 100).
  • Page 8: Ultracool Unit Description

    ULTRACOOL UNIT DESCRIPTION 3.1 SETUP OF THE ULTRACOOL UNIT (UC 2 AND UC 4) Front of the UC 4 Top panel. It gives access to the electrical box. Main power switch. Controller. Ventilation grid (on both sides, warm air exhaust).
  • Page 9 Back of the UC 4 Process water inlet connection. Process water outlet connection. Drain connection (inside the unit). Condenser (cool air intake). Characteristics plate.
  • Page 10: Setup Of The Ultracool Unit (Uc 8 To Uc 65)

    3.2 SETUP OF THE ULTRACOOL UNIT (UC 8 TO UC 65) Front of the UC 24 External controller display Status and Warning/Alarm LEDs Right panel. It gives access to the electrical box Main power switch Power and communications cables inlet (below the unit) Four wheels with locking brake (feet on UC 50 and UC 65)
  • Page 11 Back of the UC 24 Process water inlet connection Process water outlet connection Drain connection Motor fan (warm air exhaust) Condenser (cool air intake) Characteristics plate...
  • Page 12: Setup Of The Ultracool Unit (Uc 80 And Uc 100)

    3.3 SETUP OF THE ULTRACOOL UNIT (UC 80 AND UC 100) Front of the UC 100 External controller display Status and Warning/Alarm LEDs Front panel. It gives access to the electrical box Main power switch Condenser (cool air intake) Power and communications cables inlet (below the unit)
  • Page 13 Back of the UC 100 Process water inlet connection Process water outlet connection Drain connection Motor fan (warm air exhaust) Condenser (cool air intake) Characteristics plate...
  • Page 14: Identification Labels On The Ultracool Unit

    The chiller should be located as close as possible to the application. Pressure drop in the pipe should not exceed 0.7 bar. The water lines must be in pipes of at least ½” for UC 2 and UC 4 models, 1” for UC 8 to UC 24 models, 1 ½”...
  • Page 15: Electrical Connection (Uc 2 And Uc 4)

    3.6 ELECTRICAL CONNECTION (UC 2 AND UC 4) Operating voltage 230VAC +/-10%, 50Hz, 1 Ph or 230VAC +/-10%, 60Hz, 1 Ph depending on the version (see characteristic plates of the unit). In terms of Electromagnetic emissions and immunity, this unit is intended for installation in an industrial environment.
  • Page 16 Introduce the main power supply cable through the cable gland located on the base of the chiller and connect it to the incoming power terminals which are located on the left side of the X1 terminal block inside the electrical box of the chiller: For the electrical supply of the Ultracool unit, use an appropriate electrical line according to the data in the characteristics plate.
  • Page 17: Additional Electrical Connections

    3.8 ADDITIONAL ELECTRICAL CONNECTIONS The chiller also has some special terminals prepared for the following functions (introduce the required cables also through the brush gland on the right side or the base of the chiller depending on the model): Terminals 23 and 24, remote On/Off operation: This chiller can be turned On and Off automatically by an external signal.
  • Page 18: Startup

    STARTUP 4.1 OPERATING CONDITIONS Water temperature at the inlet: Nominal: 15ºC (59ºF) Maximum: 40ºC (104ºF) (1) Cold water temperature at the outlet: Nominal: 10ºC (50ºF) Minimum: 7ºC (45ºF) (2) Maximum: 35ºC (95ºF) Temperature of the ambient air: Nominal: 25ºC (77ºF) Minimum: -15ºC (5ºF) (3) Maximum:...
  • Page 19 Only an authorized technical service can adjust the antifreeze set point. The following table shows the ethylene glycol concentration and the antifreeze adjustment required: Min Ambient Temperature Glycol concentration (4) and Less than 0ºC until Less than -5ºC until antifreeze adjustment 0ºC or more -5ºC -15ºC...
  • Page 20: Chiller Startup

    4.2 CHILLER STARTUP Clean the application water circuit with tap water to be sure that there are no free particles. Otherwise, the filter element can block up during the startup process. Turn Off the Main power switch (to avoid any possibility of unexpected startup of the equipment during this operation).
  • Page 21 Close both access panels. Switch ON the general switch and, if remote On/Off is used, give a remote On signal. Finally switch the chiller On from the controller display (see point 5.3) and the unit will start up. Phase Sequence Verification (only required on 3-Phase units): Check that the working pressure of the pump is higher than the nominal pressure indicated on the characteristics plate.
  • Page 22: Chiller Controls

    CHILLER CONTROLS 5.1 CONTROL AND MONITORING ELEMENTS Controller (UC 2 and UC 4) Main Power Switch Webserver controller display Status LED (UC 8 to UC 100) Warning/Alarm LED (UC 8 to UC 100) External controller display (UC 8 to UC 100) The following elements allow controlling the chiller and monitoring its status: Status LED (UC 8 to UC 100): It blinks when the unit is turned Off and is waiting for an On signal.
  • Page 23: Uc Controller

    5.2 UC CONTROLLER Controller buttons: Alarm button: Displays the list of active alarms. It’s also used to manually reset alarms Prg button: Used to access the configuration menu (for authorized service only) Esc button: Return to the main screen Up – Down buttons: Navigate between the display screens or increase/decrease the value of a selected parameter Enter button: Used to enter a subscreen/menu from the main screen or to switch between screen navigation and the different parameters that can be modified on a particular screen...
  • Page 24: Operation

    5.3 OPERATION Remote On/Off and On/Off from the display: The unit will only turn On when it receives both an On signal from its remote On/Off contacts (circuit closed between terminals 23 and 24, see point 3.8) and it also receives an On command from the display. In the same way, the unit will turn Off either when the circuit between terminals 23 and 24 is open or when an Off command is issued from the display.
  • Page 25 Setting the language: To change the language of the display, go to the Settings screens loop (see point 5.2), press Down until the “press ENTER to change laguage” screen and press Enter to access the language configuration screen. From the new screen, press Enter to change the language and press Esc or let the timer run out to confirm the new language.
  • Page 26 Select UoM to change Select and confirm new UoM Setting the Date and Time: To change the Date and Time used by the controller, go to the Settings screens loop (see point 5.2), press Down until the “press ENTER to change Date/Time” screen and press Enter to access the Date and Time configuration screen.
  • Page 27 Information screens loop: This is a series of information screens that can be accessed from the controller display (see point 5.2). They contain information on the operation of the chiller, readings of physical sensors, software version and its serial number. Use the Up/Down buttons to navigate the different screens. Information on the pump pressure and water filter pressure drop can be found within this loop, on the “Info –...
  • Page 28: Preheating Function

    5.4 PREHEATING FUNCTION The chiller controller integrates an automated preheating system that can turn on the water pump when the temperature in the water circuit drops below a specified setpoint. The heat introduced by the pump operation maintains the water in the tank and in the rest of the circuit at the preset temperature. This system will operate as long as the general switch is turned On by turning the water pump On and Off when necessary.
  • Page 29: Ethernet Configuration

    5.5 ETHERNET CONFIGURATION The chiller can be remotely monitored and operated through any PC connected to the same network where the chiller is connected via Ethernet. To be able to access the chiller remotely it is first necessary to configure its IP address. Follow these steps on the external controller display to do so: Press the Alarm and the Enter buttons for a few seconds, until the display changes to the following screen:...
  • Page 30 Once done, it will be possible to access the webserver of the chiller from a web browser on any PC connected to the same network as the chiller. To do so, just introduce the IP number of the chiller on the navigation bar of the web browser and select the Display tile from the home page.
  • Page 31: Lauda.live Cloud Service

    Within this distinction, operating parameters are those directly shown to the user via the device display and could be changed by the user. The service parameters are only available to the LAUDA Service team. LAUDA.LIVE permissions screen: The Settings screen loop contains a screen to enable or disable the communications with the LAUDA.LIVE service and to set its access permissions.
  • Page 32: Maintenance

    MAINTENANCE 6.1 BASIC MAINTENANCE Weekly: Verify that the water temperature indicated on the controller display is approximately at the setpoint. Verify the water level in the tank. Verify the pressure drop of the water filter (on the “Info – Process circuit” screen of the Information screens loop, see point 5.3).
  • Page 33: Troubleshooting

    Use a microUSB to USB adapter if necessary. On UC 2 and UC 4 models the controller is accessible on the front of the chiller. On UC 8 to UC 100 models the controller is inside the electrical box: Turn the chiller Off with the Main Power Switch, open the lateral panel and the electrical box to reach it.
  • Page 34 UC 8 to UC 100 microUSB to USB adapter After selecting the save location, press Enter, select YES on the “Confirm:” field with the Up or Down buttons and press Enter again to begin the Log export. If the log file is saved to the Internal Flash Memory, when the service engineer is on site with the chiller, they will be able to retrieve the saved log file for analysis.
  • Page 35: Alarms And Warnings List

    7.2 ALARMS AND WARNINGS LIST See the following table for the main possible causes for an alarm or warning and their solution: FAULT CAUSE SOLUTION RESTART PROCEDURE AL145, 158, 462 or Panel(s) of the Close the panels Disconnect the chiller by housing open (only turning Off the main power HP alarm by pressure...
  • Page 36 FAULT CAUSE SOLUTION RESTART PROCEDURE AL129 or 390 Q1 circuit breaker Check if the electrical Disconnect the chiller by Circuit 1 Power+ offline tripped connections are correct. Check turning Off the main power or Alarm Offline Drive supply voltage and power surges switch (see point 5.1).
  • Page 37 FAULT CAUSE SOLUTION RESTART PROCEDURE or Phase sequence Wrong phase Switch OFF the main power Once the phase sequence is It stops the whole unit sequence at the main switch, disconnect the chiller from correct the chiller will work power supply the power supply and exchange normally automatically two phases in the main power...
  • Page 38 FAULT CAUSE SOLUTION RESTART PROCEDURE The external controller External controller Check that the cable connections The chiller is still running display shows the display cable are tight at both ends and examine normally and it accepts message „NO LINK“ or damaged or loose the total length of the cable for On/Off commands through...
  • Page 39: Technical Features

    TECHNICAL FEATURES 8.1 TECHNICAL FEATURES UC 80 UC 100 UC 2 UC 4 UC 8 UC 14 UC 24 UC 50 UC 65 kcal/h 2064 4128 8811 13565 20859 44025 57512 67948 81967 Cooling capacity 10,2 15,8 24,3 51,2 66,9...
  • Page 40: Energy Efficiency Information

    0,20 Rated energy efficiency ratio 7,64 DC,D Other items Capacity control Variable Degradation co-efficient chillers 0,90 kg CO 2 eq GWP of the refrigerant 2088 (100 years) LAUDA Ultracool S.L. – Ctra. Rubí 316, Contact details 08228 Terrassa (Barcelona), Spain...
  • Page 41 0,45 Rated energy efficiency ratio 6,74 DC,D Other items Capacity control Variable Degradation co-efficient chillers 0,90 kg CO 2 eq GWP of the refrigerant 2088 (100 years) LAUDA Ultracool S.L. – Ctra. Rubí 316, Contact details 08228 Terrassa (Barcelona), Spain...
  • Page 42 0,75 Rated energy efficiency ratio 8,79 DC,D Other items Capacity control Variable Degradation co-efficient chillers 0,90 kg CO 2 eq GWP of the refrigerant 2088 (100 years) LAUDA Ultracool S.L. – Ctra. Rubí 316, Contact details 08228 Terrassa (Barcelona), Spain...
  • Page 43 1,09 Rated energy efficiency ratio 9,78 DC,D Other items Capacity control Variable Degradation co-efficient chillers 0,90 kg CO 2 eq GWP of the refrigerant 2088 (100 years) LAUDA Ultracool S.L. – Ctra. Rubí 316, Contact details 08228 Terrassa (Barcelona), Spain...
  • Page 44 2,00 Rated energy efficiency ratio 8,05 DC,D Other items Capacity control Variable Degradation co-efficient chillers 0,90 kg CO 2 eq GWP of the refrigerant 2088 (100 years) LAUDA Ultracool S.L. – Ctra. Rubí 316, Contact details 08228 Terrassa (Barcelona), Spain...
  • Page 45 5,06 Rated energy efficiency ratio 6,65 DC,D Other items Capacity control Variable Degradation co-efficient chillers 0,90 kg CO 2 eq GWP of the refrigerant 2088 (100 years) LAUDA Ultracool S.L. – Ctra. Rubí 316, Contact details 08228 Terrassa (Barcelona), Spain...
  • Page 46 6,86 Rated energy efficiency ratio 6,38 DC,D Other items Capacity control Variable Degradation co-efficient chillers 0,90 kg CO 2 eq GWP of the refrigerant 2088 (100 years) LAUDA Ultracool S.L. – Ctra. Rubí 316, Contact details 08228 Terrassa (Barcelona), Spain...
  • Page 47 5,44 Rated energy efficiency ratio 9,82 DC,D Other items Capacity control Variable Degradation co-efficient chillers 0,90 kg CO 2 eq GWP of the refrigerant 2088 (100 years) LAUDA Ultracool S.L. – Ctra. Rubí 316, Contact details 08228 Terrassa (Barcelona), Spain...
  • Page 48 7,29 Rated energy efficiency ratio 8,76 DC,D Other items Capacity control Variable Degradation co-efficient chillers 0,90 kg CO 2 eq GWP of the refrigerant 2088 (100 years) LAUDA Ultracool S.L. – Ctra. Rubí 316, Contact details 08228 Terrassa (Barcelona), Spain...
  • Page 49: Accessories And Consumables

    ACCESSORIES AND CONSUMABLES The following accessories and consumables are available for the Ultracool units. Accessories for UC 2 and UC 4 230V/1Ph/50Hz (BSP) (1) Catalogue number IK10: 2x10m Installation Kit: Includes 2 hoses and 2 sets of fittings A000001 IK20: 2x20m Installation Kit: Includes 2 hoses and 2 sets of fittings...
  • Page 50 Accessories for UC 8 to UC 24 Catalogue number IK10: 2x10m Installation Kit: Includes 2 hoses and 2 sets of fittings A000002 IK20: 2x20m Installation Kit: Includes 2 hoses and 2 sets of fittings A000005 IK50: 2x50m Installation Kit: Includes 2 hoses and 2 sets of fittings A000007 BSP-NPT Adapters: 2 fittings male-male to convert from the female BSP on the unit A000036...
  • Page 51 (1) Use 2 litres per each 100 litres of water tank volume (2) Ready to use mixture with -7ºC (20ºF) freezing point. Do not dilute Chiller model Consumables Catalogue number UC 2 and UC 8 and UC 50 and UC 80 and UC 24...
  • Page 52: Log Book

    10 LOG BOOK 10.1 LOG BOOK Date Remarks Signature...
  • Page 53: Annexes

    Do not use automotive antifreeze. Use lab grade ethylene glycol only! Do not use an ethylene glycol concentration above 40%; this would damage the water pump. LAUDA Ultracool S.L. will not accept any warranty for any damage caused by water that is out of one or more of the above limits.
  • Page 54: Ec Declaration Of Conformity Uc 2 And Uc 4

    12 EC DECLARATION OF CONFORMITY UC 2 AND UC 4 Manufacturer: LAUDA Ultracool S.L. Ctra. Rubí 316, 08228 Terrassa – Spain Declares that under our sole responsibility for supply/manufacture of the products: Product Line: Ultracool Serial number: from 74477 Type: UC 2, UC 4...
  • Page 55: Ec Declaration Of Conformity Uc 8 To Uc 100

    13 EC DECLARATION OF CONFORMITY UC 8 TO UC 100 Manufacturer: LAUDA Ultracool S.L. Ctra. Rubí 316, 08228 Terrassa – Spain Declares that under our sole responsibility for supply/manufacture of the products: Product Line: Ultracool Serial number: from 68948 Type: UC 8, UC 14, UC 24, UC 50, UC 65, UC 80, UC 100...