1.14 INDOOR INSTALLATION.

• Type C configuration, sealed chamber and fan assisted.
Horizontal intake - exhaust kit Ø60/100.
Kit assembly (Fig. 14): install the bend with flange (2) onto the
central hole of the boiler inserting the gasket (1) and tighten
using the screws in the kit. Couple the terminal pipe (3) with
the male end (smooth) into the female end of the bend (with lip
seals) up to the stop; making sure that the internal wall sealing
plate and external wall sealing plate have been fitted, this will
ensure sealing and joining of the elements making up the kit.
Note: when the boiler is installed in areas where very rigid tem-
peratures can be reached, a special anti-freeze kit is available that
can be installed as an alternative to the standard kit.
• Coupling extension pipes and concentric elbows Ø 60/100.
To snap-fit extensions with other elements of the flue extraction
elements, operate as follows engage the concentric pipe or elbow
with the male side (smooth) on the female section (with lip seal)
up to the stop on the previously installed element. This will en-
sure sealing and joining of the elements correctly.
2
3
1
MAX. 725
4 5
The kit includes:
N°1 - Gasket (1)
N°1 - Concentric bend Ø 60/100 (2)
N°1 - Int./exhaust concentric terminal
Ø 60/100 (3)
N°1 - Internal wall sealing plate (4)
N°1 - External wall sealing plate (5)
MAX. 645
The Ø 60/100 horizontal intake/exhaust kit can be installed with
the rear, right side, left side and front outlet.
• Application with rear outlet (Fig. 15). The 970 mm pipe length
enables routing through a maximum thickness of 710 mm. Nor-
mally the terminal must be shortened. Calculate the distance by
adding the following values: Part thickness + internal projection
+ external projection. The minimum indispensable projection
values are given in the figure.
• Application with side outlet (Fig. 16); Using the horizontal in-
take-exhaust kit, without the special extensions, enables routing
through a wall thickness of 725 mm with the left side outlet and
645 with the right side outlet.
• Extensions for horizontal kit. The horizontal intake-exhaust kit Ø
60/100 can be extended up to a max. horizontal distance of 3,000
mm including the terminal with grid and excluding the concen-
tric bend leaving the boiler. This configuration corresponds to
a resistance factor of 100. In these cases the special extensions
must be requested.
Connection with N°1 extension (Fig. 17). Max. distance between
vertical boiler axis and external wall is 1855 mm.
Connection with N°2 extensions (Fig. 18). Max. distance between
vertical boiler axis and external wall is 2805 mm.
C
12
14
C
12
16
Max. 710
Max. 1870
Max. 1855
Max. 2820
Max. 2805
C
12
15
C
12
17
C
12
18