E.14.4 Relay output control
Using the fi eldbus for relay output control requires:
• drive parameter values set as defi ned below
• fi eldbus controller command(s) in the appropriate location. (The location is defi ned by the Protocol Reference, which is
protocol dependent.)
Drive Parameter
1401
RELAY OUTPUT 1
1402
RELAY OUTPUT 2
1403
RELAY OUTPUT 3
1
1410
RELAY OUTPUT 4
1411
1
RELAY OUTPUT 5
1412
1
RELAY OUTPUT 6
1. More than 3 relays requires the addition of a relay extension module.
Note: Relay status feedback occurs without confi guration as defi ned below.
Drive Parameter
0122
RO 1-3 STATUS
0123
RO 4-6 STATUS
E.14.5 Analog output control
Using the fi eldbus for analog output control (e.g. PID setpoint) requires:
• drive parameter values set as defi ned below
• fi eldbus controller command(s) in the appropriate location. (The location is defi ned by the Protocol Reference, which is
protocol dependent.)
Drive Parameter
1501
AO1 CONTENT SEL
0135
COMM VALUE 1
1502 -
AO1 CONTENT MIN
1505
- MAXIMUM AO1
1506
FILTER AO1
1507
AO2 CONTENT SEL
0136
COMM VALUE 2
1508 -
AO2 CONTENT MIN
1511
- MAXIMUM AO2
1512
FILTER AO2
E.14.6 PID Control setpoint source
Using the following settings to select the fi eldbus as the setpoint source for PID loops:
Drive Parameter
4010
SET POINT SEL (Set 1)
4110
SET POINT SEL (Set 2)
4210
SET POINT SEL (Ext/Trim)
MN796 - ACB530
Value
35 (COMM)
Relay Output 1 controlled by fi eldbus.
36 (COMM (-1))
Relay Output 2 controlled by fi eldbus.
Relay Output 3 controlled by fi eldbus.
Relay Output 4 controlled by fi eldbus.
Relay Output 5 controlled by fi eldbus.
Relay Output 6 controlled by fi eldbus.
Value
Protocol Reference
Relay 1-3 status.
Relay 4-6 status.
Value
135 (COMM)
Analog Output 1 controlled by writing to
parameter 0135.
-
Set appropriate
Used for scaling.
values.
Filter time constant for AO1.
136 (COMM)
Analog Output 2 controlled by writing to
parameter 0136.
-
Set appropriate
Used for scaling.
values.
Filter time constant for AO2.
Value
8 (COMM VALUE 1)
9 (COMM+AI1)
10 (COMM*AI1)
Description
Description
Description
Setpoint is input reference 2 (+/-/* AI1)
Protocol Reference
Protocol Reference
-
-
-
-
-
-
Protocol Reference
Fieldbus Communications E-25