8
Z e n i t h Z T S ( D ) 3 0 - 1 2 0 0 A AT S , Q U I C K S TA R T U S E R M A N U A L

Zenith ZTS(D) T-series 30-1200A features

Feature comparison
Ampere sizes available
Rated voltage
Rated frequency
Phase system
Number of poles
Neutral configuration
Switched
Product type
Open transition (I-II)
Delayed transition (I - O - II or II - O - I)
Voltage and frequency settings
Pick up SOURCE 1 Voltage
Drop out SOURCE 1 Voltage
Pick up SOURCE 2 Voltage
Drop out SOURCE 2 Voltage
Pick up SOURCE 1 Frequency
Drop out SOURCE 1 Frequency
Pick up SOURCE 2 Frequency
Drop out SOURCE 2 Frequency
Time delay settings
Override momentary SOURCE 1 Outage, sec
Transfer from SOURCE 1 to SOURCE 2, sec
Override momentary SOURCE 2 Outage, sec
Transfer from SOURCE 2 to SOURCE 1, min
Generator stop delay, min
Center-OFF delay, sec
Pre-transfer delay S1 to S2, sec
Post-transfer delay S1 to S2 , sec
Pre-transfer delay S2 to S1, sec
Post-transfer delay S2 to S1, sec
Elevator Pre-signal delay S1 to S2, sec
Elevator Post-signal delay S1 to S2, sec
Elevator Pre-signal delay S2 to S1, sec
Elevator Post-signal delay S2 to S1, sec
Load shed delay, sec
Source failure detections
No voltage
Undervoltage
Overvoltage
Phase missing
Voltage unbalance
ZTS(D) controls (Touch screen)
UL: 30-1200 A
200-480 Vac
50 / 60 Hz
Single and Three
71-99 %, 101-119 %
70-98 %, 102-120 %
71-99 %, 101-119 %
70-98 %, 102-120 %
80.5-99.5 %, 100.5-119.5 %
80-99 %, 101-120 %
80.5-99.5 %, 100.5-119.5 %
80-99 %, 101-120 %
3 and 4
Yes
Yes
Yes
0-60
0-3600
0-60
0-120
0-60
0-300
0-300
0-300
0-300
0-300
0-60
0-60
0-60
0-60
0-60
Yes
Yes
Yes
Yes
Yes