2.3 Zenith ZTX series features
Feature comparison
Ampere sizes available
Rated voltage
Rated frequency
Phase system
Number of poles
Neutral configuration
Switched
Product type
Open transition (I-II)
Voltage and frequency settings
Pick up Voltage Source 1
Drop out Voltage Source 1
Pick up Voltage Source 2
Drop out Voltage Source 2
Pick up Frequency Source 1
Drop out Frequency Source 1
Pick up Frequency Source 2
Drop out Frequency Source 2
Time delay settings
Override momentary Source 1 Outage, sec
Transfer from source 1 to source 2, sec
Override momentary Source 2 Outage, sec
Transfer from source 2 to source 1, min
Generator stop delay, min
ZTX controls (DIP)
S1
S2
l
ll
LOAD
AUTO
Auto
In-phase
Priority
Manual
config
monitor
retransfer
Start
On
No priority
On
Ok
Off
Source 1
Off
Dropout ∆U / ∆f
∆U 5% / ∆f 5%
∆U 10% / ∆f 5%
∆U 15% / ∆f 10%
∆U 20% / ∆f 10%
Generator
stop delay
S1 Failure
S1 Return
delay [s]
delay [min]
0
2
4
10
20
30 s
1
3
5
15
30
4 min
Off
On
Bypass
Lamp
Auto
load
load
time
test
test
test
delay
Alarm reset
l
ll
ON
ON
UL: 30-1200 A
200-480 Vac
50 / 60 Hz
Single and Three
2, 3 and 4
Yes
Yes
Fixed 2% above drop out
+/-5, 10, 15, 20 %
Fixed 2% above drop out
+/-5, 10, 15, 20 %
Fixed 1% above drop out
+/-5, 10 %
Fixed 1% above drop out
+/-5, 10 %
0, 1, 2, 3, 4, 5, 10, 15, 20, 30
2 (0-3600 via Ekip Connect)
1,5 (0-60 via Ekip Connect)
0, 1, 2, 3, 4, 5, 10, 15, 20, 30
30 secs or 4 mins
19
!