Auxiliary Relay Output Wiring
Relay outputs 3 and 4 are available for controlling an
auxiliary device, such as a horn annunciator.
OUTPUT
DEVICE
TWO 6-POSITION CONNECTORS
FOR RELAY OUTPUTS
Fig. 11. Relay output wiring from Security Controller to an auxiliary device.
Relay Output Wiring Notes
• Install the door strike or auxiliary output device per the
vendor's instructions.
• Use shielded, twisted-pair cabling to connect the circuit
to the Security Controller. Maximum cable distance is
2000 feet (610m)
SEC-H-602 AND SEC-H-616 SECURITY CONTROLLER
Figure 11 shows example wiring for controlling an output
device.
SHIELD
SECURITY
CONTROLLER
• Wire the door strike or auxiliary output device to the
• At the Security Controller, ground shield wires to the
19
CURRENT THROUGH SECURITY
CONTROLLER RELAYS MUST BE
LIMITED TO NO MORE THAN 3A TO
PREVENT BOARD DAMAGE. IF THE
POWER SUPPLY USED DOES NOT
PROVIDE THIS CURRENT LIMITING,
INSTALL AN EXTERNAL FUSE, AS
SHOWN HERE.
appropriate relay output on the Security Controller and
to the power supply used to power the strike or device.
Each relay output on the Security Controller has a
common terminal (C), and normally open (NO) and
normally closed (NC) terminal.
designated grounding point at the enclosure. See Fig.
5 on page 12.
DEVICE
POWER
SUPPLY
+
(AC OR DC,
24V MAX)