926TC: Installation, Start-up, Operating and Service and Maintenance Instructions
pressure to decrease input. Repeat steps b through e of Step 1
until correct low-heat input is achieved. Re-install low heat
regulator seal cap on gas valve.
i. Jumper R to W/W1, and W2. This keeps furnace locked in
high-heat operation when both W/W1 and W2 are energized.
j. Repeat items d through g for high-heat operation, repeating Step
2 and adjusting the high-heat regulator screw as required.
k. Remove jumpers R to W/W1 and R to W2.
Table 26 – Orifice Size and Manifold Pressure (in. w.c.) for Gas
Input Rate
TWO-STAGE FURNACE
(TABULATED DATA BASED ON 20,000 BTUH HIGH-HEAT / 13,000 BTUH LOW-HEAT PER BURNER,
DERATED 2%/1000 FT (305M) ABOVE SEA LEVEL)
ALTITUDE
A
V
G
.
G
A
S
RANGE
HEAT VALUE
0.58
AT ALTITUDE
Orifice Mnfld Press Orifice Mnfld Press Orifice Mnfld Press Orifice Mnfld Press
ft (m)
(Btu/cu ft)
No.
High/Low
900
43
3.8 / 1.6
0
925
43
3.6 / 1.5
(0)
950
43
3.4 / 1.4
975
44
3.7 / 1.6
to
1000
44
3.5 / 1.5
1025
44
3.3 / 1.4
2000
1050
44
3.2 / 1.3
(610)
1075
45
3.7 / 1.6
1100
46
3.7 / 1.6
U.S.A.
800
42
3.4 / 1.4
2001 (611)
825
43
3.8 / 1.6
to
850
43
3.6 / 1.5
3000 (914)
875
43
3.4 / 1.4
900
44
3.7 / 1.6
Canada
925
44
3.5 / 1.5
2001 (611)
950
44
3.3 / 1.4
to
975
44
3.2 / 1.3
4500 (1372)
1000
46
3.8 / 1.6
775
42
3.3 / 1.4
3001
800
43
3.8 / 1.6
(915)
825
43
3.6 / 1.5
850
44
3.8 / 1.6
to
875
44
3.6 / 1.5
4000
900
44
3.4 / 1.4
(1219)
925
44
3.2 / 1.4
950
45
3.7 / 1.6
750
42
3.3 / 1.4
4001
775
43
3.7 / 1.6
(1220)
800
43
3.5 / 1.5
825
44
3.8 / 1.6
to
850
44
3.5 / 1.5
5000
875
44
3.3 / 1.4
(1524)
900
44
3.2 / 1.3
925
46
3.8 / 1.6
725
42
3.2 / 1.4
5001
750
43
3.7 / 1.5
(1525)
775
43
3.4 / 1.4
800
44
3.7 / 1.6
to
825
44
3.5 / 1.5
6000
850
44
3.3 / 1.4
(1829)
875
45
3.7 / 1.6
900
46
3.7 / 1.6
675
42
3.4 / 1.4
6001
700
42
3.2 / 1.3
(1830)
725
43
3.6 / 1.5
750
43
3.4 / 1.4
to
775
44
3.6 / 1.5
7000
800
44
3.4 / 1.4
(2133)
825
44
3.2 / 1.3
850
46
3.8 / 1.6
Table 26
- Orifice Size and Manifold Pressure (in. w.c.) for Gas Input
Rate (Continued)
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
S
P
E
C
F I
C I
G
R
A
V
T I
Y
O
F
N
A
T
U
R
A
L
G
A
S
0.60
0.62
0.64
No.
High/Low
No.
High/Low
No.
High/Low
42
3.2 / 1.4
42
3.3 / 1.4
42
3.4 / 1.4
43
3.7 / 1.6
43
3.8 / 1.6
42
3.2 / 1.4
43
3.5 / 1.5
43
3.6 / 1.5
43
3.7 / 1.6
44
3.8 / 1.6
43
3.4 / 1.5
43
3.6 / 1.5
44
3.6 / 1.5
44
3.8 / 1.6
43
3.4 / 1.4
44
3.5 / 1.5
44
3.6 / 1.5
44
3.7 / 1.6
44
3.3 / 1.4
44
3.4 / 1.4
44
3.5 / 1.5
45
3.8 / 1.6
44
3.3 / 1.4
44
3.4 / 1.4
46
3.8 / 1.6
45
3.8 / 1.6
44
3.2 / 1.4
42
3.5 / 1.5
42
3.6 / 1.5
42
3.7 / 1.6
42
3.3 / 1.4
42
3.4 / 1.4
42
3.5 / 1.5
43
3.7 / 1.6
42
3.2 / 1.3
42
3.3 / 1.4
43
3.5 / 1.5
43
3.7 / 1.5
43
3.8 / 1.6
44
3.8 / 1.6
43
3.5 / 1.5
43
3.6 / 1.5
44
3.6 / 1.5
44
3.8 / 1.6
43
3.4 / 1.4
44
3.4 / 1.5
44
3.6 / 1.5
44
3.7 / 1.6
44
3.3 / 1.4
44
3.4 / 1.4
44
3.5 / 1.5
45
3.8 / 1.6
44
3.2 / 1.4
44
3.3 / 1.4
42
3.4 / 1.4
42
3.5 / 1.5
42
3.6 / 1.5
42
3.2 / 1.4
42
3.3 / 1.4
42
3.4 / 1.4
43
3.7 / 1.6
43
3.8 / 1.6
42
3.2 / 1.4
43
3.5 / 1.5
43
3.6 / 1.5
43
3.7 / 1.6
44
3.7 / 1.6
43
3.4 / 1.4
43
3.5 / 1.5
44
3.5 / 1.5
44
3.7 / 1.5
44
3.8 / 1.6
44
3.4 / 1.4
44
3.5 / 1.5
44
3.6 / 1.5
44
3.2 / 1.3
44
3.3 / 1.4
44
3.4 / 1.4
42
3.4 / 1.4
42
3.5 / 1.5
42
3.6 / 1.5
43
3.8 / 1.6
42
3.3 / 1.4
42
3.4 / 1.4
43
3.6 / 1.5
43
3.7 / 1.6
43
3.8 / 1.6
43
3.4 / 1.4
43
3.5 / 1.5
43
3.6 / 1.5
44
3.7 / 1.5
44
3.8 / 1.6
43
3.4 / 1.4
44
3.5 / 1.5
44
3.6 / 1.5
44
3.7 / 1.6
44
3.3 / 1.4
44
3.4 / 1.4
44
3.5 / 1.5
45
3.7 / 1.6
44
3.2 / 1.4
44
3.3 / 1.4
42
3.3 / 1.4
42
3.4 / 1.5
42
3.5 / 1.5
43
3.8 / 1.6
42
3.2 / 1.4
42
3.3 / 1.4
43
3.5 / 1.5
43
3.7 / 1.5
43
3.8 / 1.6
44
3.8 / 1.6
43
3.4 / 1.5
43
3.5 / 1.5
44
3.6 / 1.5
44
3.7 / 1.6
44
3.8 / 1.6
44
3.4 / 1.4
44
3.5 / 1.5
44
3.6 / 1.5
44
3.2 / 1.3
44
3.3 / 1.4
44
3.4 / 1.4
46
3.8 / 1.6
45
3.8 / 1.6
44
3.2 / 1.4
42
3.5 / 1.5
42
3.6 / 1.5
42
3.8 / 1.6
42
3.3 / 1.4
42
3.4 / 1.4
42
3.5 / 1.5
43
3.7 / 1.6
43
3.8 / 1.6
42
3.3 / 1.4
43
3.5 / 1.5
43
3.6 / 1.5
43
3.7 / 1.6
44
3.7 / 1.6
43
3.4 / 1.4
43
3.5 / 1.5
44
3.5 / 1.5
44
3.6 / 1.5
44
3.7 / 1.6
44
3.3 / 1.4
44
3.4 / 1.4
44
3.5 / 1.5
45
3.8 / 1.6
44
3.2 / 1.4
44
3.3 / 1.4
A11252A
(TABULATED DATA BASED ON 20,000 BTUH HIGH-HEAT / 13,000 BTUH LOW-HEAT PER BURNER,
DERATED 2%/1000 FT (305M) ABOVE SEA LEVEL)
ALTITUDE
A
V
G
.
G
A
S
RANGE
HEAT VALUE
AT ALTITUDE
Orifice Mnfld Press Orifice Mnfld Press Orifice Mnfld Press Orifice Mnfld Press
ft (m)
No.
(Btu/cu ft)
650
42
7001
675
43
(2134)
700
43
725
44
to
750
44
8000
775
44
(2438)
800
45
825
46
625
42
8001
650
43
(2439)
675
43
700
44
to
725
44
9000
750
44
(2743)
775
45
9001
600
42
(2744)
625
43
650
43
to
675
44
10000
700
44
(3048)
725
44
* Orifice numbers shown in BOLD are factory-installed.
4. Restore furnace to normal operating condition.
a. Turn gas valve ON/OFF switch to OFF.
b. Remove water column manometer or similar device from
manifold pressure tap.
!
FIRE HAZARD
Failure to follow this warning could result in personal injury, death,
and/or property damage.
Manifold pressure tap set screw must be tightened or 1/8-in. NPT pipe
plug must be installed to prevent gas leaks.
c. Tighten set screw on manifold pressure tap with 3/32-in. hex
wrench, or if 1/8-in. NPT plug was removed, apply pipe dope
sparingly to end of plug and re-install in the gas valve.
d. Turn gas valve ON/OFF switch to ON.
e. On the 3 digit display, navigate to (Htt) and select the setting
required for attached thermostat (1St) for single-stage
thermostats, (2St) for two-stage thermostats).
f. Check for gas leaks and verify furnace operation.
Adjust Temperature Rise
NOTE: Blower door must be installed when taking temperature rise
reading. Leaving blower door off will result in incorrect temperature
measurements, due to possible changes in duct static pressure and
airflow.
!
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in:
-
Overheating the heat exchangers or condensing flue gases in
heat exchanger areas not designed for condensate.
-
Shortened furnace life
-
Component damage.
Temperature rise must be within limits specified on furnace rating plate.
Recommended operation is at midpoint of rise range or slightly above.
The furnace must operate within the temperature rise ranges specified on
the furnace rating plate. Do not exceed temperature rise range specified
on unit rating plate. Determine the temperature rise as follows:
1. Place thermometers in return and supply ducts as near furnace as
possible. Be sure thermometers do not see heat exchanger so that
62
TWO-STAGE FURNACE
S
P
E
C
F I
C I
G
R
A
V
T I
Y
O
F
N
A
T
U
R
A
L
G
A
S
0.58
0.60
0.62
High/Low
No.
High/Low
No.
High/Low
3.4 / 1.4
42
3.5 / 1.5
42
3.6 / 1.5
3.8 / 1.6
42
3.2 / 1.4
42
3.3 / 1.4
3.5 / 1.5
43
3.7 / 1.5
43
3.8 / 1.6
3.8 / 1.6
43
3.4 / 1.4
43
3.5 / 1.5
3.5 / 1.5
44
3.7 / 1.5
44
3.8 / 1.6
3.3 / 1.4
44
3.4 / 1.4
44
3.5 / 1.5
3.8 / 1.6
44
3.2 / 1.4
44
3.3 / 1.4
3.7 / 1.6
46
3.8 / 1.6
45
3.8 / 1.6
3.4 / 1.4
42
3.5 / 1.5
42
3.6 / 1.5
3.8 / 1.6
42
3.2 / 1.4
42
3.3 / 1.4
3.5 / 1.5
43
3.6 / 1.5
43
3.7 / 1.6
3.7 / 1.6
43
3.4 / 1.4
43
3.5 / 1.5
3.5 / 1.5
44
3.6 / 1.5
44
3.7 / 1.6
3.3 / 1.4
44
3.4 / 1.4
44
3.5 / 1.5
3.7 / 1.6
44
3.2 / 1.3
44
3.3 / 1.4
3.3 / 1.4
42
3.4 / 1.5
42
3.6 / 1.5
3.7 / 1.6
42
3.2 / 1.3
42
3.3 / 1.4
3.5 / 1.5
43
3.6 / 1.5
43
3.7 / 1.6
3.7 / 1.6
44
3.8 / 1.6
43
3.4 / 1.4
3.4 / 1.4
44
3.5 / 1.5
44
3.7 / 1.5
3.2 / 1.3
44
3.3 / 1.4
44
3.4 / 1.4
WARNING
CAUTION
0.64
No.
High/Low
42
3.7 / 1.6
42
3.4 / 1.5
42
3.2 / 1.4
43
3.6 / 1.5
43
3.4 / 1.4
44
3.7 / 1.5
44
3.4 / 1.4
44
3.2 / 1.4
42
3.7 / 1.6
42
3.4 / 1.4
42
3.2 / 1.3
43
3.6 / 1.5
44
3.8 / 1.6
44
3.6 / 1.5
44
3.4 / 1.4
42
3.7 / 1.6
42
3.4 / 1.4
43
3.8 / 1.6
43
3.5 / 1.5
44
3.8 / 1.6
44
3.5 / 1.5
A11252B