8 Configuration

The option comms configuration is accessible through the keypad under the menu Option Comms,
through DSE Lite function block Option Comms Config or through the webserver following the path Home
> Engineer > Communications > Option Comms.
The AC20 EtherCAT option requires configuration of both communication parameters and process data
mapping.

8.1 Communication parameters

Keypad Menu Path
Setup
Communication
Option
The network parameters of the slave must be set to establish communication with master.
The parameter 0691 COMMS REQUIRED must be set to EtherCAT.
The parameter 2566 MASTERMAPPING must be set to choose how process data mapping is
defined. (See 8.2 Process Data for detail)
DOC-0017-07-EN: AC20 Series - EtherCAT Option
DSE-Lite Function Block
DOC-0017-07-EN-B 04.04.2023
Webserver
15 (58)