AUTOMATIC operation
Position the AUTO/MAN (2) switch on the AUTO position and set the startup switch (1) to
ON position.
The automatic function indicator (7) will light up. If the battery which supplies the
generating set has a voltage of more than 11.5 Volts, the battery charged indicator (11) will
light up. When the voltage at the ends of the 12Vdc terminals of the generating set is lower
than 11.5 Volts, the battery charged light indicator (11) will go off and the generating set
will begin the startup procedure (similar to that of the manual operation).
During the operation in automatic mode, the display (3) will show the total running hours of
the generating set. Press the hour or voltmetric switch button to display the voltage at the
ends of the 12Vdc terminals, or at the ends of the battery.
When the battery is charged, the battery charged indicator (11) will light up and the
electronic control panel will turn off the generating set.
Control and Alarm Functions
5
3 DISPLAY: when the generating set has started up, the total running hours will be
displayed. Press the hour or voltmetric switch button during the manual operation to
display the running hours after the last maintenance. Press the hour or voltmetric switch
button during the automatic operation to display the voltage at the ends of the 12Vdc
terminals, or at the ends of the battery.
4 HOUR and VOLTMETRIC SWITCH BUTTON: when in MAN (2) function, press this
button to display the running hours elapsed after the last change of the engine oil. When in
AUTO (2) function, press this button to display the voltage at the ends of the 12Vdc
terminals.
5 RESET: when the display shows any characters without logic, the panel is to be
reinitialised. Press the Reset key and, holding it down, switch on the panel. When 4 zeroes
(0000) are shown on the display, the panel is reinitialised.
6 GENERATOR RUNNING INDICATOR: this indicator flashes during proper operation of
the generating set.
7 AUTOMATIC FUNCTION INDICATOR: this pilot lamp is illuminated as long as the
AUTO (2) function is selected.
8 STARTUP FAILED INDICATOR: this pilot lamp will light up to indicate that the
generating set has not started up, after all four attempts at starting up have failed.
9 MAINTENANCE REQUEST INDICATOR: this pilot lamp flashes after 50 running hours
have elapsed and the engine oil level is to be checked. When the lamp illuminates steady,
this means that 100 running hours have elapsed and the engine oil is to be changed. Upon
every engine oil change the After-sales service must reset the Timer to make it restart
from zero. To reset the flashing light, press the switch button (4) and, holding it down,
switch on the electronic panel by means of the switch (1).
10 GAS RESERVE INDICATOR: if a reserve detector is provided in the gas tank, it is
possible to connect the suitable cable located inside the generating set (Fig. 10 Ref. 4).
This way the pilot lamp will light up when the gas level has gone below its reserve level.
11 BATTERY CHARGED INDICATOR: this pilot light is illuminated as long as the voltage
at the ends of the 12Vdc terminals, located inside the generating set, is more than 11.5
Volts.
12 MINIMUM ENGINE OIL LEVEL INDICATOR: this pilot lamp will light up to indicate that
the level of oil in the engine has gone below the minimum level. A safety system turns off
the engine automatically in order to avoid damages.
13 HIGH TEMPERATURE INDICATOR: this pilot lamp will light up when the temperature
of the generating set goes over its safety value; the engine will stop at the same time.