AUTOMATIC CONTROL PANEL DESCRIPTION

The elements making them up are:
ON/OFF switch for the start-up and switch-off function
1
AUTO/MAN switch for the automatic or manual function
2
Display
3
Hour or voltmetric switch button
4
Reset
5
Generator running indicator (flashing)
6
Automatic function indicator
7
Startup failed indicator
8
Maintenance request indicator
9
Fuel reserve indicator
10
Battery charged indicator
11
Minimum oil level indicator
12
High temperature indicator
13
MANUAL operation
Position the AUTO/MAN (2) switch on the MAN position and set the startup switch (1) to
ON position. The word WAIT will appear on the display (3) for 8 seconds. When these
have run out, the electronic control panel will start the first automatic procedure for starting
up the generating set. If the engine starts up at the end of this phase, then the generator
running indicator (6) will start to flash.
Should the engine not start up, this automatic procedure will be repeated up to 4 times. If
the engine has not started up yet at the end of this complete cycle, the startup failed
indicator (8) will light up. If only the startup failed indicator (8) stays lit, you can repeat the
startup procedure several times. If the generating set has not started up at all even after
many attempts, you will have to get in touch with the after-sales service.
During the operation in manual mode, the display (3) will show the total running hours of
the generating set. Press the hour or voltmetric switch button to display the running hours
after the last maintenance.