Epsilon Ei DeviceNet Drive Reference Manual
DN FAB Master Send Block
Ei-DN
Range
Units
The DN FAB Master Send Block displays the polled data being transferred from the master to the
drive via the Master Send fixed assembly block (FAB).
DN Host Mode
Ei-DN
Range
Units
0,1
Enabling the "Host Mode" gives the host (DeviceNet Master) exclusive control of the following
Input functions:
•
Index Select and Index Initiate
•
Jog +, Jog -, Jog Fast
•
Home Initiate
•
Define Home
•
Brake Control and Release
All other functions will be logically OR'ed with inputs and Modbus 3 when in Host mode.
Host mode is useful when access to the hardwire I/O needs to be switched from "DeviceNet only"
to "DeviceNet I/O or Hardware I/O."
DN MacID
Ei-DN
Range
Units
0-63
The DN MacID is the node address of the Ei-DN on the DeviceNet network. The range of this
number is 0-63.
26