[ VIII Troubleshooting ]

4. Voltage test points on the control board

1. TPEFYP006, 008, 012, 015, 018, 024, 027, 030, 036, 048, 054MA143A
CN2M
CN3A
CN24
SW2
SW4
CND
CNP
HWE1832A
CN32
SW3
Indoor controller board
F01
PC51(*1)
C53(*1)
Power supply board
- 28 -
F01
Fuse(AC 250V 6.3A)
CND
Power supply voltage (220 -
240VAC)
CN2M For M-NET transmission cable
connection (24 - 30VDC)
SWE
Emergency operation
SW2
Capacity setting
CN41
SW4
Function setting
CN51
SW3
Function setting
CN52
CN32
Remote start/stop adapter
CN20
CN3A
For MA remote controller cable
connection
(10 - 13 VDC (Between 1 and 3.))
CN4F
CN44
CN52
Remote display
CN22
CN51
Centralized control
SWE
CN41
JAMA standard HA terminal A
CN44
Thermistor (liquid/gas tempera-
ture)
CN4F
Float switch
CN22
For fan control
CN24
For heater control
CN20
Thermistor (Inlet temperature)
CNMF Fan motor output
1 - 4: 294 - 340 VDC
5 - 4: 15 VDC
6 - 4: 0 - 6.5 VDC
7 - 4: Stop 0 or 15 VDC
Run 7.5 VDC
(0 - 15 pulse)
CNP
Drain-up mechanism output
(200VAC)
(*1)
V
Voltage on the (-) side of PC51
FG
and C25
(Same with the voltage between 7
(+) and 4 (-) of CNMF)
V
Voltage between the C25 pins
CC
15 VDC
(Same with the voltage between 5
(+) and 4 (-) of CNMF)
Vsp Voltage between the C53 pins
0VDC (with the fan stopped)
1 - 6.5VDC (with the fan in opera-
C25(*1)
tion)
(Same with the voltage between 6
CNMF
(+) and 4 (-) of CNMF)
GB