Mounting And Installation - Emerson dixell XC650CX Installation And Operating Instructions Manual

Table of Contents

Advertisement

Analog output 1
Analog output 2
5.7 How to connect monitoring system - RS485 Serial line
The XC650CX can be connected to a monitoring system thanks to the serial output.
To convert the TTL to RS485 signal, the XJ485CX has to be used.
The XJ485CX
is a TTL/RS485 external converter. Insert it into the TTL receptacle to convert the TTL
output into a RS485 (+) and (-) signal for the monitoring system MODBUS_RTU compatible. (XWEB).
The Adr parameter is the number to identify each electronic board. Address duplication is not
permitted, in this case the communication with monitoring system is not guaranteed (the Adr is
also the ModBUS address).
6. Mounting & installation
The instruments are suitable only for internal use. Instruments shall be mounted on panel, in a
29x71 mm hole, and fixed using the special brackets supplied.
The ambient operating temperature range is between -10÷60°C.
Avoid locations subject to heavy vibration, corrosive gases or excessive dirt. The same applies to
the probes. Ensure ventilation around the instrument.
1592001431 XC650CX GB r3.5 21.07.2020
Terminals
29[+] – 30[-].
8[+] – 10[-].
78,5
70
Related parameter
AOC: Kind of signal (4-20mA/0-10V)
AOF: function
2AOC: Kind of signal (4-20mA/0-10V)
2AOF: function
59,5
71
XC650CX
6
12/56