Firing Failure; Undesired Shutdown During Operation; Final Checks - Riello RL 190/M TL Installation, Use And Maintenance Instructions

Light oil burners
Table of Contents

Advertisement

Available languages

Available languages

Burner with output regulator RWF40
See the handbook enclosed with the regulator.
8.2.3

Firing failure

If the burner does not fire, it goes into lock-out within 5 s of the
opening of the light oil valve.
8.2.4

Undesired shutdown during operation

If the flame should go out for accidental reasons during operation,
the burner will lock out in 1 s.
8.2.5

Final checks

➤ Obscure the photocell and switch off the control
devices: the burner should start and then lock-out about 5 s
after opening of the valves.
➤ Illuminate the photoresistor and switch on the control
devices: the burner should start and then go into lock-out
after about 10 s.
➤ Obscure the photocell while the burner is in operation,
the following must occur in sequence: flame extin-
guished within 1 s, and starting cycle repetition.
➤ Switch off control device TL followed by control device
TS while the burner is operating: the burner should stop.
Burner calibration
25
GB
20024198