Accessories (Optional); Burner Description; Weight - Approximate Measurements - Riello RL 190/M TL Installation, Use And Maintenance Instructions

Light oil burners
Table of Contents

Advertisement

Available languages

Available languages

4.2.2

Accessories (optional):

OUTPUT MODULATION REGULATOR KIT
Two components should be ordered:
➤ the output regulator to install on the burner;
➤ the probe to install on the heat generator.
PARAMETER TO BE CHECKED
Range
Temperature
- 100...+ 500 °°C
Pressure
0...2,5 bar
0...16 bar
4.3

Burner description

RL 190/M
Technical description of the burner
Type
PT 100
Probe with output
4...20 mA
20084080
Fig. 1
kg
121 - 123
Tab. A
7
GB
PROBE
Code
3010110
3010213
3010214
1
Ignition electrodes
2
Combustion head
3
Screw for combustion head adjustment
4
Screw for fixing fan to flange
5
Oil pressure switch
6
Pressure gauge for pressure on nozzle return
7
Pressure gauge for pressure on nozzle delivery
8
Pump
9
Non-drip nozzle holder
10 Air gate valves
11 Safety solenoid valve
12 Fan pressure test point
13 Boiler mounting flange
14 Flame stability disk
15 Slide bars for opening the burner and inspecting the com-
bustion head
16 Extensions for slide bars 15)
17 Electrical motor
18 Ignition transformer
19 Motor contactor and thermal cut-out with reset button
20 Power switch for different operations:
automatic - manual - off.
Button for:
power increase - power reduction.
21 Terminal strip
22 Fairleads for electrical connections by installer
23 Control box with lock-out pilot light and lock-out reset button
24 Flame inspection window
25 Photocell for flame presence control
26 Valve assembly with pressure regulator on nozzle return
27 Servomotor, provides adjustment of fuel delivery regulator
and of air gate valve.
When the burner is not operating the air gate valve is fully
closed in order to reduce to a minimum heat dispersion from
the boiler due to the flue draught which draws air from the
fan suction inlet.
Two types of burner failure may occur:
Control box lock-out: if the control box 23) (Fig. 1) pushbutton
lights up, it indicates that the burner is in lock-out. To reset, press
the pushbutton, no sooner than 10 s after the lock-out.
Motor trip: release by pressing the pushbutton on thermal cut-out
19)(Fig. 1).
4.3.1

Weight - approximate measurements

The weight of the burner complete with its packaging is
shown in table (Tab. A)
POWER REGULATOR
Type
Code
RWF40
3010212
20024198

Advertisement

Chapters

Table of Contents
loading

Table of Contents