The Keor SPE UPS and battery cabinet work with dangerous voltages. Only skilled technicians qualified and authorized by LEGRAND must perform ordinary maintenance operations. No part of the battery cabinet can be repaired by the user. Extraordinary maintenance operations must be carried out by LEGRAND Technical Support Service personnel.
Page 6
KEOR SPE R/T BATTERY CABINET DANGER Make sure that the UPS is turned off and the both the UPS and the battery cabinet are completely disconnected from the AC power before carrying out and maintenance, battery replacement or repair. CAUTION The batteries inside the battery cabinet are not user-replaceable.
KEOR SPE R/T BATTERY CABINET 3. Installation Package Inspection During transportation, some unpredictable situations might occur. It is recommended that you inspect the UPS’s exterior packaging. If you notice any damage, please immediately contact the dealer from whom you purchased the unit.
Page 8
KEOR SPE R/T BATTERY CABINET Positioning constraints The UPS can be installed vertically (tower-mounting) or horizontally (rack- mounting) according to the user’s desired arrangement. Do not mount the UPS with its front or rear panel facing down at any angle Keep at least 100 mm of free space in front and at the rear of the UPS for proper ventilation.
Page 9
KEOR SPE R/T BATTERY CABINET Rackmount installation 1. Attach the included bracket ears and handles to the lateral mounting holes of the UPS. The screws to be used are the M4 (12 pcs). 2. Insert the UPS into the rack and tighten the provided four screws. The screws to be used are the M5...
Page 10
KEOR SPE R/T BATTERY CABINET Installation procedure WARNING Read the safety instructions on chapter 2 before installing the battery cabinet. 1. Connect the 1st battery cabinet to the UPS using the previous instructions. 2. Turn off the DC breaker of the 2nd Battery module.
KEOR SPE R/T BATTERY CABINET 4. Troubleshooting INDICATION POSSIBLE CAUSE SOLUTION Missing battery Check battery connector and BAT Disconnected power battery breaker. 1. Check battery connector and battery breaker. The UPS has 2. Contact Legrand Technical Battery Failure detected a bad Support for more information about Product’s Battery...
Batteries may only be replaced with the same number and type. Batteries must be brand new. If the battery brand is different from the one originally installed by Legrand, the estimated battery autonomy indicated on the display of the UPS may not be reliable.
Page 13
KEOR SPE R/T BATTERY CABINET 3) Pull out the battery cover by removing the one screw 4) Remove the battery box. 5) Put the battery box back in the original location and put back to its place the battery cover.
Page 14
KEOR SPE R/T BATTERY CABINET 7) Put back the front panel of the cabinet.
Repeat this procedure every two months if the storage ambient temperature is above +25°C (+77°F). INDICATION Batteries must never be stored if partially or totally discharged. LEGRAND is not liable for any damage or bad functioning caused to the UPS by wrong warehousing of the batteries. Dismantling DANGER Dismantling and disposal operations must be carried out only by a qualified electrician.