Huawei UPS2000-G-6KRTLL Quick Manual page 18

Hide thumbs Also See for UPS2000-G-6KRTLL:
Table of Contents

Advertisement

Alar
Alarm
Severity
m ID
Name
26
Lithium
Minor
battery
excepti
on
protecti
on
27
Battery
Minor
dischar
ge est
functio
n
enable
d
All manuals and user guides at all-guides.com
Clearance
Condition
Check again
after the
fault is
rectified.
The battery
discharge
test is
complete.
Trigger
Impact on
Condition
the System
The busbar
The internal
voltage is too
switch circuit
high.
of the lithium
The
battery is
temperature
disconnected,
of the board
and the
relay and
battery
switch tube is
cannot be
too high.
charged or
The output is
discharged.
short-
circuited.
Batteries are
reversely
connected.
The output is
overloaded.
Battery
The system
discharge test
transfers to
is enabled
battery mode.
manually.
Huawei Technologies Co., Ltd.
Huawei Industrial Base, Bantian, Longgang
Shenzhen 518129 People's Republic of China
18
Suggestion
Possible cause: The
UPS is overloaded,
the host charger is
abnormal, or battery
cables are incorrectly
connected.
Measure: Check the
cable connection,
check the host status,
or reduce the load.
Measure: Turn off
the battery discharge
test mode switch.
www.huawei.com