Alarm
Alarm
Severity
ID
Name
23
Lithium
Minor
battery
low
voltage
protecti
on
24
Lithium
Minor
battery
overcur
rent
protecti
on
25
Lithium
Minor
battery
fault
All manuals and user guides at all-guides.com
Clearance
Condition
The cell or
battery
string
voltage
rises above
the
protection
threshold.
The battery
discharge
current
drops below
the
protection
threshold.
The alarm is
not cleared.
After
batteries
are reset,
check the
status
again.
Trigger
Impact on
Condition
the System
The lithium
The internal
battery voltage
switch circuit
is less than 44
of the
V.
lithium
The minimum
battery is
cell voltage is
disconnected,
less than 2.5 V.
and the
battery
cannot be
charged or
discharged.
Discharge
The internal
current ≥ 0.93
switch circuit
times of the
of the
current limit
lithium
and Vbus ≤ 40
battery is
V for 15s
disconnected,
Discharge
and the
current ≥ 0.98
battery
times of the
cannot be
current limit
charged or
and Vbus < 17
discharged.
V for 8s
The cell voltage
The internal
sampling circuit
switch circuit
is faulty.
of the
The cell
lithium
temperature
battery is
sampling circuit
disconnected,
is faulty.
and the
The cell voltage
battery
is too high or
cannot be
too low.
charged or
The cell
discharged.
temperature
increases
abnormally.
The cell voltage
is severely
unbalanced.
BMS board
circuit fault
17
Suggestion
Possible cause: The
mains power has
failed and not been
recovered for a long
time. The cell
consistency is
abnormal. The
capacity attenuation
is too fast or the
internal resistance is
too large.
Measure: If the
lithium battery
cannot be recovered
due to protection
against abnormality,
contact local
Huawei engineers to
rectify the fault.
Possible cause: The
UPS is overloaded.
The number of
working batteries is
insufficient.
Measure: Reduce the
load. Add batteries.
Possible cause:
sampling fault (see
the telecom power
manual); cell or
equalization circuit
fault; charger
converter short-
circuit, relay fault;
switch tube fault
Measure: Restart the
lithium battery. If
the fault persists,
replace the lithium
battery.