Alarm
Alarm
Severity
ID
Name
13
Phase
Minor
lock
failure
17
Bypass
Minor
abnorm
al
18
Low
Minor
lithium
battery
level
19
Abnor
Minor
mal
mains
voltage
All manuals and user guides at all-guides.com
Clearance
Condition
Phase
locking is
successful
or the
bypass is
missing.
The bypass
voltage or
frequency
recovers to
the normal
range.
The battery
voltage or
SOC rises
above the
alarm
threshold.
The mains
voltage
input
recovers.
Trigger
Impact on
Condition
the System
The inverter fails
The system
in phase locking
cannot start
within 10s.
PFC or enter
normal
mode.
The bypass
•The system
voltage or
cannot
frequency is out
transfer to
of the normal
bypass mode
range.
when a
critical alarm
is generated.
•In bypass
mode, the
power output
is
disconnected.
Communication is
The battery
normal, but the
level is close
SOC is lower than
to the cutoff
20%.
threshold. If
Communication is
there is no
abnormal, and
mains input,
the battery
the system
voltage falls to
will shut
47 V DC.
down after
working for a
period of
time.
•The mains is
The system
disconnected or
cannot work
fails.
in normal
•The mains input
mode. If this
voltage harmonic
alarm is
exceeds 10%
generated in
(square wave
normal
input is not
mode, the
supported).
system
•The mains
transfers to
frequency change
battery
rate exceeds the
mode.
phase lock rate
defined in the
specifications (2
Hz/s for a single
UPS and 1 Hz/s
for a parallel
system).
15
Suggestion
Possible cause:
The power grid
frequency is
unstable.
•Check that the
bypass
connection is
normal.
•Check that the
bypass voltage
and frequency are
within their
normal ranges.
Possible cause:
The battery
charge level is
low.
Measure: Charge
the battery.
Check whether
the mains voltage
input is normal. If
the circuit is
faulty, send the
device to the
maintenance
center.