5.11.2 Gas train

Approved according to standard EN 676 and provided separately
from the burner.

5.11.3 Gas train installation

Disconnect the electrical power using the main
switch.
DANGER
Check that there are no gas leaks.
Pay attention when handling the train: danger of
crushing of limbs.
Make sure that the gas train is properly installed
by checking for any fuel leaks.
The operator must use the required equipment
during installation.
The gas train is prearranged to be connected to the burner by the
flange 1) (Fig. 22).

5.11.4 Gas pressure

Tab. J indicates the pressure drops of the combustion head and
gas butterfly valve, on the basis of the burner operating output.
The values shown in Tab. J refer to:
Natural gas G 20 NCV 9.45 kWh/Sm
Natural gas G 25 NCV 8.13 kWh/Sm
Column 1
Combustion head pressure drop.
Gas pressure measured at test point 1)(Fig. 23), with:
combustion chamber at 0 mbar;
burner working at maximum modulating output;
combustion head set as on page 21.
Column 2
Pressure loss at gas butterfly valve 2)(Fig. 23) with maximum
opening: 90°.
To calculate the approximate output at which the burner oper-
ates:
subtract the pressure in combustion chamber from the gas
pressure measured at test point 1)(Fig. 23).
Find, in Tab. J related to the burner concerned, the pressure
value closest to the result of the subtraction.
Read off the corresponding output on the left.
20126903
Installation
3
3
(8.2 Mcal/Sm
)
3
3
(7.0 Mcal/Sm
)
22
GB
20128345
1 p (mbar)
kW
G 20
G 25
9500
60
89
10000
63
94
10500
69
103
11100
76
113
11600
84
125
12200
92
137
12700
101
150
13200
109
162
13700
116
173
14300
122
182
9503
23
34
10200
27
40
10900
31
46
11600
35
52
12400
41
61
13100
46
69
13800
51
76
14500
56
83
15200
62
92
15560
66
98
15200
58
86
15700
62
92
16300
67
100
16800
71
106
17400
76
113
17900
81
121
18500
87
130
19000
92
137
19600
98
146
20100
104
155
1
Fig. 22
2 p (mbar)
G 20
G 25
17
25
19
28
21
31
23
34
25
37
27
40
29
43
31
46
33
49
36
54
13
19
14
21
15
22
16
24
17
25
18
27
20
30
22
33
24
36
26
39
11
16
13
19
16
24
19
28
21
31
24
36
27
40
30
45
33
49
36
54
Tab. J