• The rack design must support the total weight of the installed enclosures. Incorporate stabilizing
features suitable to prevent the rack from tipping or being pushed over during installation or normal
use.
• The rack design must consider the maximum enclosure operating ambient temperature of 35-degrees C
(95-degrees Fahrenheit).
• The rack must have a safe electrical distribution system. It must provide overcurrent protection for the
enclosure and must not be overloaded by the total number of enclosures installed. Observer the
electrical power consumption rating that is shown on the nameplate.
• The electrical distribution system must provide a reliable ground for each enclosure in the rack.
Power requirements for each power supply
To aid in power and cooling requirements planning, Table 7 on page 6 lists the rating of each power
supply unit (PSU) by enclosure. Each enclosure contains two AC PSUs for redundancy. The power rating
values represent the total power that is drawn by both PSUs. The power that is used by the system
depends on various factors, including the number of enclosures and drives in the system and the ambient
temperature.
Table 7. Power specifications per power supply
Model and type
PSU
Storwize V5000E
AC 800 W
control enclosures
Storwize V5000E
DC 800 W
control enclosures
(optional)
2072-92F or 2072-
2400 W (2)
E92 Expansion
enclosure with 92,
3.5-inch form factor
SAS drive slots
Note: One or more C19 power distribution units (PDU) are needed in the rack to connect power to the
power supplies of the 5U expansion enclosure.
The measurements that are shown in the following tables were obtained in the specific operating
environment and under the conditions described. These measurements are presented as an illustration;
measurements that are obtained in other operating environments might vary. Conduct your own testing to
determine specific measurements for your environment.
Table 8 on page 6 shows examples of the power ratings of Storwize V5000E systems with different
drive configurations.
Table 8. Power rating examples for control enclosures and drives
Control
Enclosure
Type
Storwize
800 GB Flash
V5010E
6 IBM Storwize V5000E : Storwize V5000E Quick Installation Guide
Input power
requirements
Single phase
AC: 100 V to
127 V or 200 V
to 240 V
Frequency: 50 -
60 Hz
-48 V to -60 V
DC
180 V to 264 V
single phase AC
at a frequency
of 47 Hz to 63
Hz
Drive Information
Quantity
Block Size
16
4 K
256 K
Maximum input
Maximum
current
power output
100 V to 127 V
800 W
9 A
200 V to 240 V
4.5 A
-48 V to -60 V
800 W
25 A
16 A
2400 W
Requires a C19
power socket
(C19 power
distribution
unit)
Average
230
248
Caloric value
(BTU/hr)
2730
2730
8189
Watts
Peak
Idle
231
225
263
225