Refer to our repair and calibration section at www.aemc.com/calibration. Serial #: Catalog #: 2135.45, 2135.49, 2135.50, 2135.60 & 2135.61 Model #: 6471 Please fill in the appropriate date as indicated: Date Received: Date Calibration Due: Chauvin Arnoux , Inc. ®...
1. INTRODUCTION Thank you for purchasing an AEMC Instruments Ground Tester Model 6471. ® For the best results from your instrument and for your safety, you must read the enclosed operating instructions carefully and comply with the precautions for use.
(thunderstorms). It is up to the operator to decide whether to continue or postpone measurements in these situations. Ground Resistance Tester Model 6471 - User Manual...
® Ground Tester Model 6471 Kit (300 ft - no probes included) ..Cat. #2135.60 Includes meter, (2) carrying bags, (2) 300 ft color-coded leads on spools (red/blue), (2) 100 ft color-coded leads (hand-tied, green/black),...
Replacement - Power Adapter 110/240 V & Power Cord 115 V US ..Cat. #5000.13 Replacement - Power Cord 115 V US Plug........Cat. #5000.14 Order Accessories and Replacement Parts Directly Online Check our Storefront at www.aemc.com/store for availability Ground Resistance Tester Model 6471 - User Manual...
The Model 6471 is CAT IV rated to 50 V and is over voltage protected to more than 250 V against accidental connection to live circuits. The voltage is also displayed on screen.
Grounding standards IEC 61557 parts 4 and 5 compliant Includes DataView software for data storage, real-time display, analysis, ■ ® report generation and system configuration 2.3 CONTROL FEATURES Ω GROUND TESTER MODEL 6471 Figure 2-1 Ground Resistance Tester Model 6471 - User Manual...
OFF after the function is complete. Press the DISPLAY button to turn it back ON. NOTE 3: In the Set-up mode, pressing the DISPLAY button also selects the next configurable parameter. Ground Resistance Tester Model 6471 - User Manual...
Page 15
Indicates the battery charge condition; the segments represent the energy. EARTH Indicates whether the 3-Pole EARTH measurement or the COUPLING EARTH COUPLING measurement has been selected. S x 1/10 Symbol not used in Model 6471 Ground Resistance Tester Model 6471 - User Manual...
Page 16
Indicates the alarm is activated. An audible alarm will sound if ALARM the value measured is above the limit defined in the SET-UP mode. Distances to be entered between earth electrode and supplementary electrodes or between earth electrodes. Ground Resistance Tester Model 6471 - User Manual...
Hz/OPTIONS: Enables configuration of measurement functions. Hz/OPTIONS/ DISTANCE: Available for soil resistivity and V potential DISTANCE measurements. It allows the setting of values of distances used for Rho (ρ) calculation. Ground Resistance Tester Model 6471 - User Manual...
31 (excessive external voltage) or 32 (voltage measurement overrange). If terminals H (Z) and E (X) are put into contact with the line voltage, the protection fuse will blow. Ground Resistance Tester Model 6471 - User Manual...
0.1 to 40.0 A (1): The Model 6471 cannot detect whether a current clamp SR182 or MN82 is connected. In the case of the MN82 clamp, with currents >10 A and frequencies < 100 Hz the instrument will not display any warning messages.
The START button must be pressed for more than 2 s. For frequencies between (41 and 256) Hz, the resistance of the auxiliary earth electrodes is measured at the test frequency set. At higher frequencies the resistance is measured at 256 Hz. Ground Resistance Tester Model 6471 - User Manual...
Page 22
Same characteristics as 4-Pole earth measurements with the following particular conditions: Minimum current: SR182, I >0.5 mA MN82, I >2 mA Maximum R ratio: SR182, (R ) <500 MN82, (R ) <120 with R <20 Ω Ground Resistance Tester Model 6471 - User Manual...
S-ES is the resistance of the earth rods R assumed to be ρ ρ ρ ρ identical. NOTE: With a test voltage U of 16 V, halve the value of R Ground Resistance Tester Model 6471 - User Manual...
0.1 Ω SR182 ± (20 % + 2 cts) Operating error (without external current) MN82 not specified Observe the minimum distance between the two clamps according to table in § 5.7. (1): Ground Resistance Tester Model 6471 - User Manual...
When the device is used outside this range, 1.5 %/10 °C and 1.5 % between (75 and 90) % RH must be added to the operating error. Ground Resistance Tester Model 6471 - User Manual...
Emissions in residential environment. Electrical safety according to EN 61010. Measurement according to EN 61557. CAT IV, 50 V Pollution Degree 2 *Specifications are subject to change at any time without notice Ground Resistance Tester Model 6471 - User Manual...
START/STOP button. ■ View the result on the display and toggle through the relevant parameters using the DISPLAY button. To record the information into memory, use the MEM button (see § 7). ■ Ground Resistance Tester Model 6471 - User Manual...
4.2 INSTRUMENT CONFIGURATION (SET-UP MODE) To configure the Model 6471 parameters, turn the rotary switch to SET-UP: ■ All the segments on the display are activated for 1 second and then the PUSH button message appears on the display. Various parameters are accessible by pressing the corresponding button.
5.2 RESISTANCE MEASUREMENT MΩ (2-WIRE) WARNING:: Before performing the resistance test, verify that the sample under test is not energized. 1. Set the switch to 2. Connect the resistance to terminals H (Z) and E (X). Ground Resistance Tester Model 6471 - User Manual...
3. The 6471 makes a measurement with a positive current (R+), then reverses the direction of the current and makes another measurement with negative (R-). ± ± Ω Ω (R+) + (R-) ALARM ALARM Ω Ω Ω Ω AUTO AUTO 4.
Choose a low (<) or ON or OFF type of alarm high (>) alarm Set the value of the alarm Complete the adjustment between 1 and 999 Ω of the alarm setting Ground Resistance Tester Model 6471 - User Manual...
(H, S, ES and E will all blink) Hz/OPTIONS again WARNING: Before performing the resistance test, verify that the sample under test is not energized. 1. Set the switch to 2. Connect the resistance to all 4 terminals. Ground Resistance Tester Model 6471 - User Manual...
(cables, rails, fences, etc.). Ground Resistance Tester Model 6471 - User Manual...
Page 34
8. Start the measurement by pressing the START/STOP button. EARTH Ω AUTO AUTO 9. To display the measurement parameters, press DISPLAY several times. The device displays the following parameters: , U-Act (U and its frequency, U and its frequency). Ground Resistance Tester Model 6471 - User Manual...
A distinct plateau should result as shown below. R30 R40 % H - E Take the average of the 3 or 4 readings on the R40 + R50 + R60 + R70 plateau to obtain the earth electrode resistance. Ground Resistance Tester Model 6471 - User Manual...
Avoid routing the connecting cables of the earth electrodes near or parallel to other cables (transmission or supply), metallic conductors, rails, or fences: high test frequencies may cause cross-talk and affect the measurements. Ground Resistance Tester Model 6471 - User Manual...
3. Start the measurement by pressing the START/STOP button. Ω AUTO 4. To display the measurement parameters, press DISPLAY several times. The device displays the following parameters: , U-Act (U and its frequency, U and its frequency). Ground Resistance Tester Model 6471 - User Manual...
For this selective earth measurement you need a current clamp, either an SR182 (provided) or an MN82 (available as an accessory). These two types of current clamps are specially designed to work with the 6471 ground tester. The SR182 is more precise, suited to the measurement of higher currents (up to...
Page 39
8. To measure the resistances of auxiliary electrodes H (Z) and S (Y), or if the resistance of the electrodes is too large (see § 10.1), start the measurement with a long press of the START/STOP button. will be displayed. Ω kΩ > 2s kΩ AUTO Ground Resistance Tester Model 6471 - User Manual...
DC soundings will on DC soundings will be limited to simple, be limited to simple, horizontal; layered horizontal; layered structures structures. Source: DC Resistivity - T. Boyd Ground Resistance Tester Model 6471 - User Manual...
AUTO CONFIG AUTO To switch back to the Wenner method, simply repeat this procedure. The last measurement method selected (Wenner or Schlumberger) is stored in memory when the device is switched off. Ground Resistance Tester Model 6471 - User Manual...
3. Connect the cables to the electrodes, then to terminals H (Z), S (Y), ES (Xv), and E (X) in sequence. 4. Program the distance into the instrument as described in § 5.6.3. Ground Resistance Tester Model 6471 - User Manual...
3. Drive the electrodes to a depth p of not more than 1/20 of d. 4. Connect the cables to the electrodes, then to terminals H (Z), S (Y), ES (Xv), and E (X). Ground Resistance Tester Model 6471 - User Manual...
Page 44
START/STOP button. and R , then R and R will be displayed. P-ES ρ ρ Ω Ω > 2s kΩ kΩ kΩ kΩ AUTO AUTO Ground Resistance Tester Model 6471 - User Manual...
LOOP WARNING: Use only SR182 or MN82 current clamps, which are specially designed to operate with the Model 6471. 1. Set the switch to 2. Connect a clamp to terminal H (Z) and clamp it to a point down stream from the rod under test that is a serial path to the earth.
Page 46
WARNING: In the AUTO mode, the measurement frequency is 1611 Hz. To make an earth measurement that is free of inductive effects, you must change to MANUAL mode and choose a lower measurement frequency (see § 6.2). Ground Resistance Tester Model 6471 - User Manual...
USr, 55 Hz, 92 Hz, 110 Hz, 119 Hz, 128 Hz (128 Hz is default). To change the user frequency (USr), press the ▲▼ buttons (▲▼ raises the value, and + ▲▼ lowers it). Table of possible USr frequencies (48 values from (41 to 513) Hz): Ground Resistance Tester Model 6471 - User Manual...
Pressing on Hz/OPTIONS in MANUAL mode allows the following parameters to be changed using the ► button: ■ EARTH blinks Earth Coupling Measurement 128 Hz blinks Test Frequency Measurement ■ ■ Test voltage blinks Test Voltage Selection Ground Resistance Tester Model 6471 - User Manual...
H (Z) connected to earth 1 and terminal E (X) to earth 2. Record this result by pressing the MEM button twice. EARTH COUPLING 4 and the results of the measurements are displayed. Ground Resistance Tester Model 6471 - User Manual...
► button: blinks (Wenner method) Switch to ρ (Schlumberger method) ■ ρ ■ 128 Hz blinks Change the test frequency ■ Test voltage blinks Switch between (16 and 32) V Ground Resistance Tester Model 6471 - User Manual...
In the manual mode, you can activate or deactivate the smoothing of the mea- surement results by pressing the 2nd + DISPLAY (SMOOTH) buttons. This smoothing consists in displaying an exponential mean value, a significant help with highly fluctuating values. Ground Resistance Tester Model 6471 - User Manual...
It will be possible to overwrite values already stored with new ones having the same distance d, or even to add new results having other values for the distance d provided that all of the other measurement parameters are identical. Ground Resistance Tester Model 6471 - User Manual...
To delete the test, press the ▲ button to change the blinking NO to YES, then press and hold down (>2 s) the MEM button. To exit without erasing, perform a short press on the MEM button. Ground Resistance Tester Model 6471 - User Manual...
Page 54
When a test is deleted, its Object/Test number is removed from memory. When you subsequently view stored tests, this number will be skipped. This Object/Test number combination remains unavailable for storing tests until you completely erase memory, as instructed in Section 7.3.1. Ground Resistance Tester Model 6471 - User Manual...
® recommend that you select Ground Tester and deselect the rest. You should also check the option DataView Core, which is a requirement if you plan to ® create DataView reports. ® Ground Resistance Tester Model 6471 - User Manual...
For further information about using the Ground Tester Control Panel, consult the Help system that comes with the product. Access this Help by clicking the option Help in the Control Panel’s menu bar at the top of the screen. Ground Resistance Tester Model 6471 - User Manual...
ES (Xv) in the display, the fuse must be replaced. WARNING: For safety reasons this fuse must always be replaced by an identical model: 0.63 A F 250 V 5 x 20 mm 1.5 kA (Cat. #2135.81). Ground Resistance Tester Model 6471 - User Manual...
Page 58
12. Put the lid back onto the battery case and screw it shut. 13. Wipe off any dirt on the seal and housing rim. 14. Put the unit back into the housing and screw it into place. Ground Resistance Tester Model 6471 - User Manual...
Battery is too cold for a fast charge (<0 °C) - charging at a lower current bAtt FULL Battery is full - switch to trickle charging The 6471 tester can also be charged from a 12 V car outlet with a special charging unit.
(the four cylindrical holes on the back must slip over the four mounting pins on the front panel). Also make sure you do not pinch the battery leads or other wires or components. Ground Resistance Tester Model 6471 - User Manual...
Page 61
(3 to 5 times). Discharge cycle (15 H) can be made with the instrument in MANUAL mode, DC 2-Pole (2-Pole) resistance measurement and a short-circuit between H (Z) and E (X) plugs. Ground Resistance Tester Model 6471 - User Manual...
S (Y) leg of the circuit. To reduce the resistance of the electrodes, you can also drive them deeper, pack the ground around them well, or dampen them with water. Ground Resistance Tester Model 6471 - User Manual...
≤ 513 Hz > 30 kΩ flashes 4P sel < 1 mA flashes Values measured (U, I, steady R) unstable, varying by more than 5 % about flashes their mean values. Ground Resistance Tester Model 6471 - User Manual...
(when the NOISE symbol is no longer illuminated). 10.1.5 Error Messages When started up, the Model 6471 device automatically performs a self-test. If a fault appears during this self-test or during a measurement, the device displays a message in the form Err XX.
(603) 742-2346 E-mail: repair@aemc.com (Or contact your authorized distributor.) Contact us for the costs for repair, standard calibration, and calibration traceable to N.I.S.T. NOTE: You must obtain a CSA# before returning any instrument. Ground Resistance Tester Model 6471 - User Manual...
AEMC Instruments will repair or replace the faulty material ® at our discretion. www.aemc.com/warranty.html REGISTER ONLINE AT: Ground Resistance Tester Model 6471 - User Manual...
(603) 749-6434 (Ext. 360) Fax: (603) 742-2346 E-mail: repair@aemc.com Caution: To protect yourself against in-transit loss, we recommend that you insure your returned material. NOTE: You must obtain a CSA# before returning any instrument. Ground Resistance Tester Model 6471 - User Manual...
Resistivity of the earth (ρ) Resistivity is defined as the resistance from wall to opposite wall of a cubic meter of soil. It is measured in ohm-meters (Ωm). Ground Resistance Tester Model 6471 - User Manual...
Page 69
(cf. step voltage). The general term earth measurement can refer to measurements of individual earth electrodes, earth connections or entire earthing systems, depending on the object of interest. Ground Resistance Tester Model 6471 - User Manual...
2 earth sockets (R first earth value calculated (R second earth value calculated (R coupling resistance between earths R and R = (R – R ) / 2) Ground Resistance Tester Model 6471 - User Manual...
Page 71
In both cases, this value on the display is associated with its frequency. In this case, the resistances of the 4 stakes used for measurement are indicated by R P-ES Ground Resistance Tester Model 6471 - User Manual...