Step 5 - Field Fabricate Ductwork; Step 6 - Rig And Place Unit - Bryant 548J A Series Installation Instructions Manual

Single package rooftop heat pump with puron (r--410a) refrigerant
Table of Contents

Advertisement

Fig. 4 - - Unit Leveling Tolerances
Step 5 — Field Fabricate Ductwork
Cabinet return-air static pressure (a negative condition)
shall not exceed 0.35 in. wg (87 Pa) with economizer or
0.45 in. wg (112 Pa) without economizer.
For vertical ducted applications, secure all ducts to roof
curb and building structure. Do not connect ductwork to
unit.
Insulate and weatherproof all external ductwork, joints,
and roof openings with counter flashing and mastic in
accordance with applicable codes.
Ducts passing through unconditioned spaces must be
insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return
MAX WEIGHT
UNIT
LB
548J*04A
755
548J*05A
760
548J*06A
840
548J*07A
880
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Hook rigging shackles through holes in base rail, as shown in detail "A." Holes in base rails are centered around the
unit center of gravity. Use wooden top to prevent rigging straps from damaging unit.
MAXIMUM ALLOWABLE
DIFFERENCE IN. (MM)
A-B
B-C
A-C
0.5" (13)
1.0" (25)
1.0" (25)
C06110
KG
IN
343
74.38
345
74.38
381
74.38
399
74.38
Fig. 5 - - Rigging Details
should be ducted through the roof deck to comply with
applicable fire codes.
For units with accessory electric
applications require a minimum clearance to combustible
surfaces of 1- - in (25 mm) from duct for first 12- - in (305 mm)
away from unit. Vertical applications do not require a
minimum clearance.
Minimum clearancis not required around ductwork.
Step 6 — Rig and Place Unit
Keep unit upright and do not drop. Spreader bars are not
required if top crating is left on unit. Rollers may be used
to move unit across a roof. Level by using unit frame as a
reference. See Table 1 and Fig. 5 for additional
information.
Lifting holes are provided in base rails as shown in Fig. 5.
Refer to rigging instructions on unit.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in
equipment damage.
All panels must be in place when rigging. Unit is not
designed for handling by fork truck.
Before setting the unit onto the curb, recheck gasketing on
curb.
DIMENSIONS
A
B
MM
IN
1889
36.25
1889
36.25
1889
35.63
1889
37.25
7
heaters: Horizontal
CAUTION
C
MM
IN
MM
921
33.38
848
921
33.38
848
905
41.38
1051
946
41.38
1051
C06005

Advertisement

Table of Contents
loading

This manual is also suitable for:

548j-04a548j-05a548j-06a548j-07a

Table of Contents