Bryant 548J A Series Installation Instructions Manual page 23

Single package rooftop heat pump with puron (r--410a) refrigerant
Table of Contents

Advertisement

OAQ Sensor/RH Sensor
SEN
COM
24 VAC
Fig. 42 - - RTU- - MP / Outdoor CO
(33ZCSENCO2) Connections
On 548J***A units equipped with factory- - installed
Smoke Detector(s), the smoke
implements the unit shutdown through its NC contact set
connected to the unit's CTB input. The FSD function is
initiated via the smoke detector's Alarm NO contact set.
The RTU- - MP controller communicates the smoke
detector's tripped status to the BAS building control. See
Fig. 29, RTU- - MP System Control wiring schematic.
The
Fire
Shutdown
MENU
Config
Inputs
normally open status of this input when there is no fire
alarm.
Connecting Discrete Inputs
Filter Status
The filter status accessory is a field- - installed accessory.
This accessory detects plugged filters. When installing
this accessory, the unit must be configured for filter status
by setting MENU
Config
to Filter Status and normally open (N/O) or normally
closed (N/C). Input 8 or 9 is recommended for easy of
installation. Refer to Fig. 28 and Fig. 30 for wire
terminations at J5.
Fan Status
The fan status accessory is a field- - installed accessory.
This accessory detects when the indoor fan is blowing air.
When installing this accessory, the unit must be
configured
for
fan
MENU
Config
Inputs
Status and normally open (N/O) or normally closed (N/C).
Input 8 or 9 is recommended for easy of installation. Refer
to Fig. 28 and Fig. 30 for wire terminations at J5.
Remote Occupancy
The remote occupancy accessory is a field- - installed
accessory. This accessory overrides the unoccupied mode
and puts the unit in occupied mode. When installing this
accessory, the unit must be configured for remote
occupancy by setting MENU
5, 8, or 9 to Remote Occupancy and normally open (N/O)
or normally closed (N/C).
Also set MENU
Schedules
on/off. Input 8 or 9 is recommended for easy of
installation. Refer to Fig. 28 and Table 3 for wire
terminations at J5.
J4-5
J4-6
C08463
Sensor
2
detector controller
Switch
configuration,
input
5,
identifies
Inputs
input 3, 5, 8, or 9
status
by
setting
input 3, 5, 8, or 9 to Fan
Config
Inputs
input 3,
occupancy source to DI
Power Exhaust (output)
Connect the accessory Power Exhaust contactor coil(s) per
Fig. 43.
Power Exhaust
PEC
Fig. 43 - - RTU- - MP Power Exhaust Connections
Space Relative Humidity Sensor - - The RH sensor is not
used with 548J***A models at this time.
Communication Wiring - - Protocols
General
the
Protocols are the communication languages spoken by
control devices. The main purpose of a protocol is to
communicate information in the most efficient method
possible. Different protocols exist to provide different
kinds of information for different applications. In the BAS
application, many different protocols are used, depending
on manufacturer. Protocols do not change the function of
a controller; just make the front end user different.
The RTU- - MP can be set to communicate on four different
protocols: BACnet, Modbus, N2, and LonWorks. Switch 3
(SW3) on the board is used to set protocol and baud rate.
Switches 1 and 2 (SW1 and SW2) are used to set the
board's network address. See Fig. 44 for the switch setting
per protocol. The 3rd party connection to the RTU- - MP is
through plug J19.
NOTE: Power must be cycled after changing the SW1- - 3
switch settings.
Refer to the RTU- - MP 3rd Party Integration Guide for
more detailed information on protocols, 3rd party wiring,
and networking.
23
TAN
J11-3
CTB
THERMOSTAT
C
GRA