7.5. HEATING STOPPING

Function to prevent actuators from switching on at specified time intervals.
➢ Date settings
Heating Off – sets the date from which the heating will be switched off
Heating on - sets the date from which the heating will be switched on
➢ Weather control - When the external sensor is connected, the main screen will display the external temperature,
while the controller menu will display the mean external temperature.
The function based on the outside temperature allows to determine the mean temperature, which will work on the basis of
the temperature threshold. If the mean temperature exceeds the specified temperature threshold, the controller will switch
off the heating of the zone in which the weather control function is active.
Enabled – to use the weather control, the selected sensor must be enabled
Averaging time – the user sets the time on the basis of which the mean outside temperature will be calculated.
Setting range is from 6 to 24 hours.
Temperature threshold – a function protecting against excessive heating of the respective zone. The zone in which
the weather control is switched on will be blocked from overheating if the mean daily outdoor temperature exceeds
the set threshold temperature. For example, when temperatures rise in the Spring, the controller will block
unnecessary room heating.

7.6. ANTI-STOP SETTINGS

If the anti-stop function is activated, the pump starts, preventing scale from building up in the event of prolonged inactivity
of the pump. Activation of this function allows you to set the operating time of the pump and the operating intervals of this
pump.

7.7. MAXIMUM HUMIDITY

If the current humidity level is higher than the set maximum humidity, the cooling of the zone will be disconnected.
The function is only active in

7.8. DHW SETTINGS

By enabling the DHW function, the user has the option to set the mode of operation: time, constant or schedule.
Time mode - the DHW pre-set temperature will only be valid for the set time. The user can change the contact status
by clicking
Active
temperature is displayed.
Constant mode - the DHW setpoint temperature will apply constantly. It is possible to change the contact status by
clicking
Active
or Inactive.
Schedule – by enabling this option, we additionally select
and times of the DHW pre-set temperature.
DHW hysteresis - is the difference between the pre-set temperature on the boiler (when the DHW pump is switched
on) and the temperature of its return to operation (switching on). In the case of the pre-set temperature of 55
and hysteresis of 5
Cooling
mode, provided that a sensor with humidity measurement is registered in the zone.
or Inactive. After clicking on the option, the screen for editing the duration of the pre-set
o
C, the DHW pump is switched on again after the temperature has dropped to 50
Settings, where we have the option to set specific days
20
o
C
o
C.