Measurement setup
VEGABAR 81 • Secondary Device for electronic differential pressure
Fig. 12: Measurement setup for density measurement, h = distance between the
two measuring points
1
VEGABAR 81, Primary Device
2
VEGABAR 81, Secondary Device
The mounting distance " h" of the two sensors should be at least
10 %, better 20 %, of the final value of the sensor measuring range. A
bigger distance increases the accuracy of the density measurement.
Slight density changes cause only slight changes of the measured
differential pressure. The measuring range must hence be selected
accordingly.
Note:
The density measurement is possible in open as well as in closed
vessels.
4.9

Density-compensated level measurement

Keep the following in mind when setting up the measuring system:
Mount the Primary Device below the min. level
Mount the Secondary Device above the Primary Devices
Mount both sensors away from the filling stream and emptying and
protected against pressure shocks from the stirrer
4 Mounting
2
1
21