Measurement setup
VEGABAR 81 • Slave sensor for electronic differential pressure
Fig. 11: Measurement setup for density measurement, h = distance between the
two measuring points
1
VEGABAR 81
2
VEGABAR 81, slave sensor
The mounting distance h of the two sensors should be at least 10 %,
better 20 %, of the final value of the sensor measuring range. A bigger
distance increases the accuracy of the density measurement.
Slight density changes cause only slight changes of the measured
differential pressure. The measuring range must hence be selected
accordingly.
The density measurement is possible in open as well as in closed
vessels.
4.9

Density-compensated level measurement

The master/slave combination is suitable for density-compensated
level measurement
Keep the following in mind when setting up the measuring system:
Mount the master sensor below the min. level
Mount the slave sensor above the master sensor
Mount both sensors away from the filling stream and emptying and
protected against pressure shocks from the stirrer
4 Mounting
2
1
21