5.5.1.4 Examples
examples of settings:
DS-8 AC-in-1
DS-7 AC-in-1
DS-6 AC-in-1
DS-5 AC-in-2
DS-4 Charging current
DS-3 Charging current
DS-2 Stand-alone mode
DS-1 Stand-alone mode
Step1, stand-alone
Example 1 (factory setting):
8, 7, 6 AC-in-1: 50A
5 AC-in-2: 30A
4, 3 Charge current: 75%
2, 1 Stand-alone mode
To store the settings after the required values have been set: press the 'Up' button for 2 seconds (upper button to the right of
the DIP switches, see appendix A, position K). The overload and low-battery LED's will flash to indicate acceptance of the
settings.
We recommend making a note of the settings, and filing this information in a safe place.
The DIP switches can now be used to apply the remaining settings (step 2).
5.5.2 Step 2: Other settings
The remaining settings are not relevant for slaves.
Some of the remaining settings are not relevant for followers (L2, L3). These settings are imposed on the whole system by the
leader L1. If a setting is irrelevant for L2, L3 devices, this is mentioned explicitly.
ds8-ds7: Setting charging voltages (not relevant for L2, L3)
Absorption
Float
ds8-ds7
voltage
oltage
off
off
56.4
55.2
off
on
57.6
55.2
on
off
58.8
55.2
on
on
60.0
55.2
ds6: absorption time 8 or 4 hours (not relevant for L2, L3)
ds5: adaptive charging characteristic (not relevant for L2, L3)
ds4: dynamic current limiter
ds3: UPS function
ds2: converter voltage
ds1: converter frequency (not relevant for L2, L3)
(the wide input frequency range (45-55Hz) is 'on' by default)
Note:
-
If "adaptive charging algorithm" is on, ds6 sets the maximum absorption time to 8 hours or 4 hours.
-
If "adaptive charging algorithm" is off, the absorption time is set to 8 hours or 4 hours (fixed) by ds6.
18
on
DS-8
on
on
DS-7
on
on
DS-6
on
on
DS-5
on
DS-4
on
DS-3
on
off
DS-2
off
DS-1
off
Step1, stand-alone
Example 2:
8, 7, 6 AC-in-1: 50A
5 AC-in-2: 16A
4, 3 Charge: 100%
2, 1 Stand-alone
Storage
Suitable for
voltage
Gel Victron Long Life (OPzV)
52.8
Gel Exide A600 (OPzV)
Gel MK battery
Gel Victron Deep Discharge
Gel Exide A200
52.8
AGM Victron Deep Discharge
Stationary tubular plate (OPzS)
AGM Victron Deep Discharge
Tubular plate (OPzS) batteries in
52.8
semi-float mode
AGM spiral cell
Tubular plate (OPzS) batteries in
52.8
cyclic mode
DS-8
DS-7
on
DS-6
on
off
DS-5
DS-4
on
DS-3
on
off
DS-2
off
DS-1
Step1, stand-alone
Example 3:
8, 7, 6 AC-in-1: 16A
5 AC-in-2: 16A
4, 3 Charge: 100%
2, 1 Stand-alone
on = 8 hours
off = 4 hours
on = active
off = inactive (fixed absorption time)
on = active
off = inactive
on = active
off = inactive
on = 120V
off = 125V
on = 50Hz
off = 60Hz
off
DS-8
on
DS-7
on
DS-6
off
off
DS-5
on
DS-4
off
DS-3
on
off
DS-2
off
off
DS-1
off
Step1, stand-alone
Example 4:
8, 7, 6 AC-in-1: 30A
5 AC-in-2: 30A
4, 3 Charge: 50%
2, 1 Stand-alone