Condensate Trap - Carrier N96MSN Installation, Start-Up, Operating And Service And Maintenance Instructions

Single-stage, high efficiency, 4-way multipoise 35-in. (889 mm), condensing gas furnace
Table of Contents

Advertisement

N96MSN: Installation, Start-up, Operating and Service and Maintenance Instructions
openings in doors or floors having free area of at least 2
in.2/1,000 BTUh (4,400 mm2/kW) of total input rating of all gas
appliances.
2. An attic or crawlspace may be considered a space that freely
communicates with the outdoors provided there are adequate
permanent ventilation openings directly to outdoors having free
area of at least 1-in.2/4,000 BTUh of total input rating for all gas
appliances in the space.
3. In spaces that use the Indoor Combustion Air Method, infiltration
should be adequate to provide air for combustion, permanent
ventilation and dilution of flue gases. However, in buildings with
unusually tight construction, additional air MUST be provided
using the methods described in the Outdoor Combustion Air
Method section.
4. Unusually tight construction is defined as Construction with:
a. Walls and ceilings exposed to the outdoors have a continuous,
sealed vapor barrier. Openings are gasketed or sealed and
b. Doors and openable windows are weatherstripped and
c. Other openings are caulked or sealed. These include joints
around window and door frames, between sole plates and floors,
between wall-ceiling joints, between wall panels, at penetrations
for plumbing, electrical and gas lines, etc.
Combination of Indoor and Outdoor Air
1. Indoor openings shall comply with the Indoor Combustion Air
Method below and,
2. Outdoor openings shall be located as required in the Outdoor
Combustion Air Method mentioned previously and,
3. Outdoor openings shall be sized as follows:
a. Calculate the Ratio of all Indoor Space volume divided by
required volume for Indoor Combustion Air Method below.
b. Outdoor opening size reduction Factor is 1 minus the Ratio in a.
above.
c. Minimum size of Outdoor openings shall be the size required in
Outdoor Combustion Air Method above multiplied by reduction
Factor in b. above. The minimum dimension of air openings shall
be not less than 3 in. (80 mm).

CONDENSATE TRAP

Condensate Trap - Upflow Orientation
When the furnace is installed in the upflow position, it is not necessary
to relocate the condensate trap or associated tubing. Refer to
upflow condensate trap information. Refer to Condensate Drain section
for information how to install the condensate drain.
Condensate Trap
Relief Port
Collector Box
Plugs
UPFLOW TRAP CONFIGURATION
Fig. 8 – Upflow Trap Configuration
(Appearance may vary)
Condensate Trap - Downflow Orientation.
When the furnace is installed in the downflow position, the condensate
trap will be initially located at the upper left corner of the collector box,
as received from the factory. See the top image in
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Fig. 8
Vent Pipe Clamp
Vent Elbow Clamp
Vent Elbow
Collector Box
Plug
Condensate Trap
Relief Port
Condensate Trap
Pressure Switch
Outlet
Port
1 & 2 Stage Units
Fig.
9. When the
furnace is installed in the downflow orientation, the condensate trap
must be relocated for proper condensate drainage. See the bottom image
in
Fig.
9.
Fig. 9 – Downflow Trap Configuration
for
A11307
11
(Appearance may vary)
A11587
A230046

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents