Carrier N95ESN Installation, Start-Up, Operating And Service And Maintenance Instructions

Carrier N95ESN Installation, Start-Up, Operating And Service And Maintenance Instructions

Single-stage, high efficiency, 4-way multipoise condensing gas furnace

Advertisement

N95ESN
Single-Stage, High Efficiency, 4-Way Multipoise
35-in. (889 mm), Condensing Gas Furnace
NOTE: Read the entire instruction manual before starting the
installation.

TABLE OF CONTENTS

WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury and/or
death.
Carbon Monoxide (CO) is a colorless, odorless, and tasteless poisonous
gas that can be fatal when inhaled. Follow all installation, maintenance,
and service instructions. See additional information below regarding
the installation of a CO Alarm.
REQUIRED NOTICE FOR MASSACHUSETTS INSTALLATIONS
IMPORTANT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Table 1 - Minimum Clearances to Combustible Materials for All Units
4
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 2 - Loose Parts Bag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
CODES AND STANDARDS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
DURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
AIR FOR COMBUSTION AND VENTILATION . . . . . . . . . . . . . . 8
Table 3 - Minimum Free Area Required for Each Combustion Air
Opening or Duct to Outdoors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Table 4 - Minimum Space Volumes for 100% Combustion, Ventila-
tion and Dilution Air from Outdoors . . . . . . . . . . . . . . . . . . . . . . . 9
CONDENSATE TRAP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
CONDENSATE DRAIN CONNECTION . . . . . . . . . . . . . . . . . . . . 12
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Table 5 - Opening Dimensions - In. (mm) . . . . . . . . . . . . . . . . . 16
Table 6 - Air Filter Selection and Duct Sizing - In. (mm) . . . . . 18
Table 7 - Filter Media Pressure Drop (Clean) Versus Airflow - In.
W.C. (Pa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table 8 - Filter Media Pressure Drop (Clean) Versus Face Velocity-
In. W.C. (Pa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
AIR DUCTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
GAS PIPING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Table 9 - Maximum Capacity of Pipe . . . . . . . . . . . . . . . . . . . . . 22
ELECTRICAL CONNECTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Table 10 - Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
VENTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Table 11 - Vent Termination Kit for Direct Vent (2-pipe) Systems28
Table 12 - Maximum Equivalent Vent Length - Ft. . . . . . . . . . . 37
Table 13 - Deductions from Maximum Equivalent Vent Length - Ft.
Portions of the text and tables are reprinted from NFPA 54/ANSI Z223.1E, with permission of National Fire Protection Association, Quincy, MA
02269 and American Gas Association, Washington DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI
Installation, Start-up, Operating and
Service and Maintenance Instructions
on the referenced subject, which is represented only by the standard in its entirety.
(M) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Table 14 - Maximum Allowable Exposed Vent Length in Uncondi-
tioned Space - Ft. / M. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Table 15 - Hanger Spacing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Table 16 - Approved Combustion-Air and Vent Pipe, Fitting and Ce-
ment Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Table 17 - Altitude Derate Multiplier for U.S.A. . . . . . . . . . . . . 48
Table 18 - Gas Rate (CU ft./hr). . . . . . . . . . . . . . . . . . . . . . . . . . 50
Table 19 - Blower Off Delay Jumper Positions . . . . . . . . . . . . . 51
Table 20 - Air Delivery - CFM (With Filter) . . . . . . . . . . . . . . . 51
Table 21 - Orifice Size and Manifold Pressure (in. w.c.) for Gas Input
Rate
40,000 BTUH to 140,000 BTUH. . . . . . . . . . . . . . . . . . . . . . . . . 53
Table 22 - Orifice Size and Manifold Pressure (in. w.c.) for Gas Input
Rate
26,000 BTUH ONLY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
SERVICE AND MAINTENANCE PROCEDURES. . . . . . . . . . . . 54
WINTERIZATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
PARTS REPLACEMENT INFORMATION GUIDE . . . . . . . . . . . 66
MODEL NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Most states in the USA and jurisdictions in Canada have laws that
require the use of Carbon Monoxide (CO) alarms with fuel burning
products. Examples of fuel burning products are furnaces, boilers, space
heaters, generators, water heaters, stoves/ranges, clothes dryers,
fireplaces, incinerators, automobiles, and other internal combustion
engines. Even if there are no laws in your jurisdiction requiring a CO
Alarm, it's highly recommended that whenever any fuel burning product
is used in or around the home or business that the dwelling be equipped
with a CO Alarm(s). The Consumer Product Safety Commission
recommends the use of CO Alarm(s). The CO Alarm(s) must be
installed, operated, and maintained according to the CO Alarm
manufacturer's instructions. For more information about Carbon
Monoxide, local laws, or to purchase a CO Alarm online, please visit the
following website. https://www.kidde.com.
Use of the AHRI Certified TM Mark indicates
a manufacturer's participation in the program.
For verification of certification for individual
products, go to www.ahridirectory.org .
A200326

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the N95ESN and is the answer not in the manual?

Questions and answers

Linda
May 14, 2025

Is this furnace also for cooling my home

Summary of Contents for Carrier N95ESN

  • Page 1: Table Of Contents

    N95ESN Single-Stage, High Efficiency, 4-Way Multipoise 35-in. (889 mm), Condensing Gas Furnace Installation, Start-up, Operating and Service and Maintenance Instructions NOTE: Read the entire instruction manual before starting the (M) ..........38 Table 14 –...
  • Page 2: Important

    N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions REQUIRED NOTICE FOR MASSACHUSETTS INSTALLATIONS IMPORTANT The Commonwealth of Massachusetts requires compliance with regulation 248 CMR as follows: 5.08: Modifications to NFPA-54, Chapter 10 2) Revise 10.8.3 by adding the following additional requirements: a.
  • Page 3: Safety Considerations

    N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions NOTE: ALL DIMENSIONS IN INCH (MM) U.S. ECCN: Not Subject to Regulation (N.S.R.) SD5660-4 REV. - A210210 Fig. 1 – Dimensional Drawing SHIP WT. FURNACE SIZE LB (KG) CABINET WIDTH OUTLET WIDTH...
  • Page 4 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions in minor personal injury or product and property damage. NOTE and WARNING NOTICE are used to highlight suggestions which will result in enhanced installation, reliability, or operation. FIRE HAZARD 1. Use only with type of gas approved for this furnace. Refer to the furnace rating plate.
  • Page 5: Introduction

    N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions The furnace should be sized to provide 100 percent of the design heating NOTICE load requirement plus any margin that occurs because of furnace model size capacity increments. None of the furnace model sizes can be used if IMPORTANT INSTALLATION AND START-UP PROCEDURES the heating load is 12,000 BTU or lower.
  • Page 6: Codes And Standards

    N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions Duct Systems WARNING • US and CANADA: Current edition of Air Conditioning Contractors Association (ACCA) Manual D, Sheet Metal and Air Conditioning FIRE, INJURY OR DEATH HAZARD Contractors National Association (SMACNA), or American Society...
  • Page 7: Accessories

    N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions damage. If the control is to be installed in a furnace, follow items 1 WARNING through 4 before bringing the control or yourself in contact with the furnace. Put all used and new controls into containers before CARBON MONOXIDE POISONING / COMPONENT touching ungrounded objects.
  • Page 8: Air For Combustion And Ventilation

    N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions AIR FOR COMBUSTION AND VENTILATION • U.S.A. Installations: Current edition of Section 9.3 of the NFPA 54/ANSI Z223.1, Air for Combustion and Ventilation and applicable Introduction provisions of the local building codes.
  • Page 9 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions Table 4 – Minimum Space Volumes for 100% Combustion, Ventilation and Dilution Air from Outdoors OTHER THAN FAN-ASSISTED TOTAL FAN-ASSISTED TOTAL (1,000’S BTUH GAS INPUT RATE) (1,000’S BTUH GAS INPUT RATE)
  • Page 10: Condensate Trap

    N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions permanent ventilation openings directly to outdoors having free WARNING area of at least 1-in.2/4,000 BTUh of total input rating for all gas appliances in the space. CARBON MONOXIDE POISONING HAZARD 3. In spaces that use the Indoor Combustion Air Method, infiltration Failure to follow this warning could result in personal injury or death.
  • Page 11 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions Remove the screw that secures the Remove pressure switch tube from condensate trap to the collector box front pressure switch and discard. A If alternate vent position and remove trap. new tube is shipped in the loose parts bag.
  • Page 12: Condensate Drain Connection

    N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions To Relocate the Condensate Trap: NOTICE • Orient the furnace in the downflow position. • Fig. 9 shows the condensate trap and tubing before and after The field-supplied, accessory horizontal drain trap grommet is ONLY relocation.
  • Page 13 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions from sagging or being dislocated from the furnace or termination point. In the absence of local codes, consult the current edition of the National Standard Plumbing Code, in the U.S. or the National Plumbing Code of Canada in Canada.
  • Page 14 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions 16. Open the spring clamp and insert the long end of the adapter or the 1/2-in. CPVC pipe into the outlet stub on the drain tube. 17. Connect additional condensate piping to a code-approved drain, or...
  • Page 15: Installation

    N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions condensate and compatible with mineral and vegetable oils, such as UPFLOW DOWNFLOW HORIZONTAL canola oil. PERFORATED DISCHARGE DUCT 90° 90° FLANGE Allow at least 1/4-in. per foot (20 mm per meter) of slope down and away from the furnace in horizontal sections of drain line.
  • Page 16 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions • Special Base, NAHA01101SB • Cased Coil Assembly Part No. EAM4X, END4X, ENW4X, EAD4X • Coil casing model number NAEA HORIZONTAL TOP RETURN NOT 1. Determine application being installed from Table...
  • Page 17 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions Table 5 – Opening Dimensions - In. (mm) (Continued) Upflow Applications on Combustible or Noncombustible Flooring 21-5/8 16-5/8 22-1/4 (Subbase not required) (406) (549) (422) (565) Downflow Applications on Noncombustible Flooring...
  • Page 18 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions Filter Arrangement Due to the relatively high pressure drops of 1-in. (25 mm) thick after-market filter media, it is recommended that the filtration system be WARNING designed for at least 2-in. (51 mm) thick media.
  • Page 19: Pa)

    N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions Table 7 – Filter Media Pressure Drop (Clean) Versus Airflow - In. W.C. (Pa) Representative After-Market Filter Media Factory-Accy 14 x 25 Filter Washable Fiberglass Pleated (1-in. / 2.5 cm) (1-in. / 2.5 cm) (2-in.
  • Page 20 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions Leveling Legs (If Desired) COMBUSTION - AIR PIPE (SEE VENTING SECTION) In upflow position with side return inlet(s), leveling legs may be used. Fig. 28. Install field-supplied, 5/16 x 1-1/2 in. (8 x 38 mm) (max) corrosion-resistant machine bolts, washers and nuts.
  • Page 21: Air Ducts

    N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions GAS PIPING The bottom closure panel on furnaces of widths 17-1/2-in. (445 mm) and larger may be used for flame roll-out protection when bottom of furnace WARNING is used for return air connection. See Fig.
  • Page 22 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions PRESSURE TESTING BELOW ½ psig: Left Side Gas Entry. Gas Pipe Gas Pipe Grommet Required The furnace must be isolated from the gas supply piping by closing its Grommet Required For Direct For Direct Vent Applications Vent Applications.
  • Page 23: Electrical Connections

    N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions ELECTRICAL CONNECTIONS WARNING WARNING FIRE HAZARD Failure to follow this warning could result in personal injury, death, or ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD property damage. Failure to follow safety warnings could result in dangerous operation, Do not connect aluminum wire between disconnect switch and furnace.
  • Page 24 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions External Electrical Box on Furnace Casing CAUTION NOTE: Check to ensure that external electrical box does not interfere with duct work, gas piping or the indoor coil drain. See Fig. 30 FURNACE MAY NOT OPERATE HAZARD alternate electric entry through top panel.
  • Page 25 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions 4. Pull furnace power wires through 1/2-in. (12 mm) diameter hole in J-Box. If necessary, loosen power wires from strain—relief wire-tie on furnace wiring harness. 5. Connect field ground wire and factory ground wire to green ground screw on J-Box mounting bracket as shown in Fig.
  • Page 26 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions the HUM and COM/24V screw terminal on the control board thermostat strip. Fig. HEAT OFF-DELAY J2 DEFEAT JUMPER SELECT JUMPER Alternate Power Supplies HEAT OFF-DELAY PLT -FACTORY RUN TEST PORT PRODUCTION USE ONLY This furnace is designed to operate on utility generated power which has a smooth sinusoidal waveform.
  • Page 27: Venting

    N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions manufacturers installation instructions, and proper use of primer and NOTICE cement. All fire stop and roof flashing used with this system must be UL listed material. Acceptability under Canadian standard CAN/CSA B149 OPTIONAL VENTING BELOW THE FURNACE is dependent upon full compliance with all installation instructions.
  • Page 28 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions NOTICE RECOMMENDED SUPPORT FOR VENT TERMINATION It is recommended that sidewall vent terminations of over 24 inches (0.6 M) in length or rooftop vent terminations of over 36 inches (1 M)
  • Page 29 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions Vent systems must be composed of pipe, fittings, cements, and primers listed to ULC S636. M&G DuraVentRPolyProR or Centrotherm InnoflueR polypropylene venting systems are ULC S636 listed. NOTE: When using polypropylene venting systems, all venting materials used, including the vent terminations must be from the same manufacturer.
  • Page 30 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions ¾ in. (222mm) for 3 in. (76mm) ¾ in. (172mm) for 2 in. (51mm) 12 in. (305mm) min. separation between bottom of combustion air and bottom of vent (Typ.) A13305 Fig. 39 – Combustion Air and Vent Pipe Termination for Direct Vent (2-Pipe) System...
  • Page 31 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions A12326 Fig. 41 – Direct Vent Termination Clearance NOTE: The following is based upon National codes for gas appliances and is provided as a reference. Refer to local codes which may supersede these standards and/or recommendations.
  • Page 32 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions A12325 Fig. 42 – Ventilated Combustion Air and Non-Direct Vent Termination Clearance NOTE: The following is based upon National codes for gas appliances and is provided as a reference. Refer to local codes which may supersede these standards and/or recommendations.
  • Page 33 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions 3. Termination or termination kit should be positioned where vent WARNING vapors will not damage plants/shrubs, air conditioning equipment or utility meters. CARBON MONOXIDE POISONING HAZARD 4. Do not locate termination directly into prevailing winds.
  • Page 34 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions No operable windows, doors or Clearance distances for intakes of any type within the items greater than 3 feet shaded areas of Wall A and B. (1 meter ) away from the...
  • Page 35 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions and/or five feet of pipe may be used to accomplish the sound attenuation Ventilated Combustion function. Air intake pipe WARNING Pipe hangar CARBON MONOXIDE POISONING HAZARD 3” (76 mm) Failure to follow the instructions outlined below for each appliance being placed into operation could result in carbon monoxide poisoning or death.
  • Page 36 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions Table 12 minus the number of fittings multiplied by the deduction for each type of fitting used from Table FURNACE NOT IN HORIZONTAL SECTION OPTIONAL TERMINATION BRACKET FOR 2-PIPE PIPE DIAMETER...
  • Page 37 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions trap drain and the evaporator coil drain empty into an open segment of NOTICE pipe above the drain. See Fig.13. When using the External Vent Trap Kit, refer to those instructions for proper drain connections.
  • Page 38 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions Table 13 – Deductions from Maximum Equivalent Vent Length - Ft. (M) Pipe Diameter (in): 1-1/2 2-1/2 Mitered 90º Elbow (2.4) (2.4) (2.4) (2.4) (2.4) Medium Radius 90º Elbow (1.5) (1.5) (1.5)
  • Page 39 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions Configure the Furnace WARNING CARBON MONOXIDE POISONING HAZARD Any other unused knockout may be used Failure to follow this warning could result in personal injury or death. for combustion air connection.
  • Page 40 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions Rotate vent elbow to required position. Any other unused knockout may be used for combustion air connection. A11312A DOWNFLOW RIGHT CONFIGURATION Requires Accessory Vent Kit See Product Data for Current Kit Number...
  • Page 41 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions Notes for venting options ALTERNATE 1. Attach vent pipe adapter with gasket to furnace casing. COMBUSTION AIR CONNECTIONS 2. Align notches in rubber coupling over standoffs on adapter. Slide clamps over the coupling.
  • Page 42 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions Maximum Allowable Exposed Vent Length in Unconditioned Space (Metric) Unit Size 26,000* BTUH 0” Insulation 3/8” Insulation 1/2” Insulation Pipe Dia. Winter Design 15.2 13.7 18.3 15.2 Temp °C 40,000* BTUH...
  • Page 43 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions inside of socket to prevent buildup of excess cement. Apply second WARNING coat. DO NOT CEMENT POLYPROPYLENE FITTINGS. 14. While cement is still wet, twist pipe into socket with 1/4-in. turn.
  • Page 44 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions Optional Installation of the Vent Pipe Loosely assemble concentric vent/combustion termination components together using instructions in kit. NOTE: THIS TECHNIQUE Slide assembled kit with rain shield REMOVED through hole in wall or POLYPROPYLENE VENTING SYSTEMS.
  • Page 45 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions termination, or pair of vent terminations, must be at least 36 in. (914 NOTICE mm) away from the first two terminations. It is important that vent terminations be made as shown in Fig.
  • Page 46 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions Venting System Length Calculations The Total Equivalent Vent Length (TEVL) for EACH combustion air or vent pipe equals the length of the venting system, plus the equivalent length of elbows used in the venting system from Table Standard vent terminations or factory accessory concentric vent terminations count for zero deduction.
  • Page 47: Start-Up, Adjustment, And Safety Check

    N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions START-UP, ADJUSTMENT, AND SAFETY 3. Pour one quart (liter) of water into funnel/tube. Water should run through collector box, overfill condensate trap, and flow into open CHECK field drain. NOTICE 4. Remove funnel; replace collector box drain plug.
  • Page 48 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions Adjustments NOTICE WARNING If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size. Never FIRE HAZARD redrill an orifice. A burr-free and squarely aligned orifice hole is Failure to follow this warning could result in personal injury, death essential for proper flame characteristics.
  • Page 49 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions (Furnace is shipped with No. 44 orifices. In this example, all main screwdriver) counterclockwise (out) to decrease input rate or burner orifices are the correct size and do not need to be changed to clockwise (in) to increase input rate.
  • Page 50 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions c. Run furnace for 3 minutes. NOTICE d. Measure time (in sec) for gas meter to complete one revolution and note reading. The 2 or 5 cubic feet dial provides a more For 40,000 BTUH models through 120,000 BTUH models: DO NOT accurate measurement of gas flow.
  • Page 51 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions • Increase blower speed to reduce temperature rise. WARNING • Decrease blower speed to increase temperature rise. Change the blower heat taps as required to maintain proper temperature FIRE HAZARD rise for Heating and Cooling as described above. To change blower...
  • Page 52 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions Table 20 – Air Delivery - CFM (With Filter) (Continued) SPEED EXTERNAL STATIC PRESSURE (IN.W.C.) WIRE LEAD 2, 3 UNIT SIZE TAPS COLOR (Function) 5, 6 Cooling. Do not use for heating...
  • Page 53: Btuh To 140,000 Btuh

    N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions Check Safety Controls Table 21 – Orifice Size and Manifold Pressure (in. w.c.) for Gas Input Rate The flame sensor, gas valve, and pressure switch were all checked in the 40,000 BTUH to 140,000 BTUH Start-up procedure section as part of normal operation.
  • Page 54: Btuh Only

    N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions SERVICE AND MAINTENANCE PROCEDURES Table 22 – Orifice Size and Manifold Pressure (in. w.c.) for Gas Input Rate Untrained personnel can perform basic maintenance functions such as 26,000 BTUH ONLY cleaning and replacing air filters. All other operations must be performed by trained service personnel.
  • Page 55 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions Component Self-Test Example: Nominal break point on pressure switch is 0.68-in. W.C. The minimum break point of the switch is 0.63-in. W.C. The maximum break NOTE: The furnace control component test allows all components to point of the switch is 0.73-in.
  • Page 56 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions 7. Check operation of accessories per manufacturer’s instructions. 4. Inspect burner compartment before each heating season for rust, corrosion, soot or excessive dust. If necessary, have furnace and 8. Review Owner’s Manual with owner.
  • Page 57 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions To ensure long life, economy, and high efficiency, clean accumulated dirt and grease from blower wheel and motor annually. The inducer and blower motors are pre-lubricated and require no additional lubrication. These motors can be identified by the absence of...
  • Page 58 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions 12. Spin the blower wheel by hand to verify that the wheel does not rub 8. Disconnect Flame Sensor wire from Flame Sensor. on the housing. 9. Support the manifold and remove the 4 screws that secure the 13.
  • Page 59 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions 12. Connect the wire for the Hot Surface Igniter. b. Carefully withdraw the igniter and bracket assembly through the front of the burner assembly without striking the igniter on NOTE: Use propane-resistant pipe dope to prevent leaks. Do not use surrounding parts.
  • Page 60 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions 6. Disconnect the condensate trap relief hose from collector box port pressure, insufficient or poor quality combustion air, improper vent and condensate trap. termination, incorrect size or damaged manifold orifice(s), improper gas, or a restricted heat exchanger (primary or secondary).
  • Page 61: Winterization

    N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions WINTERIZATION CAUTION Since the furnace uses a condensing heat exchanger, some water will accumulate in the unit as a result of the heat transfer process. Therefore, UNIT COMPONENT DAMAGE HAZARD once it has been operated, it cannot be turned off and left off for an...
  • Page 62 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions valve GV open. If the burner flame is not proved within two sec, prepurge period, then shut off for 24 sec then come back on at the control CPU will close the gas valve GV, and the control HEAT speed.
  • Page 63 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions A200517 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 64 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions A190092 Fig. 71 – Troubleshooting Guide (Cont) Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 65 N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions 344443-2 Rev D A210135 Fig. 72 – Wiring Diagram Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 66: Parts Replacement Information Guide

    N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions PARTS REPLACEMENT INFORMATION GUIDE Casing Group Gas Control Group Blower door Burner Bottom plate Flame sensor Control door Gas valve Door knob assembly Hot surface igniter Top filler plate Manifold Orifice...

This manual is also suitable for:

A series

Table of Contents

Save PDF