Replacement Of Damper Motor, Air - Bentone B 45 A2.2R Installation And Maintenance Instruction

Hide thumbs Also See for B 45 A2.2R:
Table of Contents

Advertisement

7.5

Replacement of damper motor, air

1.
Disconnect the main power and shut off the fuel supply.
!
Before obtaining access to electrical and fuel line components
all supply circuits must be disconnected.
Note the connection position of the cables on the damper motor.
2.
Disconnect cables from damper motor.
3.
4.
Release the damper motor.
5.
Remove the screws (L) securing the damper motor mounting plate.
6.
Turn the damper approx. 60°.
7.
Lift up the damper motor.
Loosen (R) the control arm from the motor shaft.
8.
9.
Remove the damper motor from the mounting plate (S).
10.
Install the new damper motor on the mounting plate.
11.
Fit the control arm on the damper motor shaft. It is important that the
screw is perpendicular to the plane of the shaft.
12.
Connect the damper motor cable.
13.
Refi t the damper motor and mounting plate on the air intake. Make
sure the damper shaft is properly mounted.
14.
Release the button on the damper motor.
15.
Switch on the main power and open the fuel supply.
16.
Start burner and check/adjust combustion.
When servicing/replacing components that aff ect combustion,
!
fl ue gas analysis and soot test must be carried out following
installation.
30
Bentone
Note the connection
!
position of the cables
on the damper motor.
S
R
165 405 45

Advertisement

Table of Contents
loading

Table of Contents